2009-05-08 12:14:49 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR EXAMPLES
 OF DEFICIENCIES.
  
 2} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3).
 FOR THE NEW A/C EQUIPMENT.
  
 3} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN
 IS NEW OR EXISTING. IF NEW LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE, DISCONNECTS AND PANELS SO
 THAT COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE
 REVIEWED
  
 4} THE BREAKER SIZES LISTED ON THE PANEL SCHEDULE FOR
 THE AIR HANDLERS IS TOO LARGE TO PROTECT 7500 W UNITS
 PER 310.16. 7500/240=31.25X 1.25= 39 AMPS OR A 40 AMP
 BREAKER UNLESS ANOTHER SIZE OR RATING IS REQUIRED BY
 THE MANUFACTURER.
  
 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  