| 2009-05-08 12:14:49 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | |
| | 1} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| | 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR EXAMPLES |
| | OF DEFICIENCIES. |
| | |
| | 2} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3). |
| | FOR THE NEW A/C EQUIPMENT. |
| | |
| | 3} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN |
| | IS NEW OR EXISTING. IF NEW LOCATE ALL SERVICE EQUIPMENT |
| | ON THE PLAN, METER ENCLOSURE, DISCONNECTS AND PANELS SO |
| | THAT COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE |
| | REVIEWED |
| | |
| | 4} THE BREAKER SIZES LISTED ON THE PANEL SCHEDULE FOR |
| | THE AIR HANDLERS IS TOO LARGE TO PROTECT 7500 W UNITS |
| | PER 310.16. 7500/240=31.25X 1.25= 39 AMPS OR A 40 AMP |
| | BREAKER UNLESS ANOTHER SIZE OR RATING IS REQUIRED BY |
| | THE MANUFACTURER. |
| | |
| | 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| | FS, RESPECTIVELY. |
| | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| | IF EXEMPTIONS APPLY. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |