| Plan Review Notes For Permit 09040579 |
| Permit Number |
09040579 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-11-03 14:27:03 | REVIEWED TRUSS DRAWINGS FOR CODE COMPLIANCE. | | | | | | CORRECTIONS TO THE TRUSS ANCHOR SCHEDULE ON SHEET S-4 | | | ARE REQUIRED. ANCHOR MARK 05 SHOULD BE USC 63 BECAUSE | | | THE ROOF PITCH IS 6:12. ANCHOR MARK 6.1 SHOULD ALSO BE | | | USC 63 WITH AN UPLIFT CAPACITY OF 11,150 #. A SIGNED | | | AND SEALED LETTER OF CLARIFICATION FROM THE DESIGNER OF | | | RECORD AS DISCUSSED WITH THE ARCHITECT WILL BE | | | ACCEPTABLE. |
|