| Plan Review Notes For Permit 09040579 |
| Permit Number |
09040579 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-10-20 11:18:26 | TRUSS DRAWINGS ARE DENIED | | | CORRECTIONS ARE REQUIRED. | | | | | | 1) THE FLOOR TRUSS AND LOWER ROOF LAYOUT SPECIFIES THE | | | DESIGN CRITERIA AS FBC 07 / ASCE 7-05 AND EXPOSURE B. | | | THE TRUSS DRAWING COVERSHEET SPECIFIES EXPOSURE C. THE | | | LOWER ROOF TRUSS DRAWINGS IN THIS PACKAGE SPECIFY ASCE | | | 7-02 AND EXPOSURE B WITH TCDL OF 5 PSF AND BCDL OF 5 | | | PSF. PLEASE COORDINATE THE DESIGN CRITERIA AND LOADS | | | WITH THE APPROVED PLANS. THE PLANS WERE PERMITTED UNDER | | | THE 2004 FBC / ASCE 7-02 AND EXPOSURE B. | | | | | | NOTE: YOU CAN DESIGN THE TRUSSES USING FBC 2007 AND | | | ASCE 7-05, HOWEVER, BECAUSE OF THE CHANGES TO THE | | | EXPOSURE CATEGORY DETERMINATIONS IN THE 2009 REVISIONS | | | TO FBC 07, THE STRUCTURE IS IN EXPOSURE CATEGORY C | | | USING THIS DESIGN CRITERIA. | | | | | | 2) THE TRUSS LAYOUT DRAWINGS ARE REQUIRED TO BE SIGNED | | | AND SEALED BY THE TRUSS ENGINEER. THE SIGNATURE ON THE | | | TRUSS DRAWING COVER SHEET IS REQUIRED TO BE AN ORIGINAL | | | WET SIGNATURE, PHOTO-COPIES, STAMPS, ETC. ARE NOT | | | ALLOWED. FAC 61G-15-23.002 AND FS 471. ELECTRONIC | | | SIGNATURES OR DIGITAL SIGNATURES ARE ONLY USED FOR | | | PLANS OR OTHER DOCUMENTS ARE TRANSMITTED | | | ELECTRONICALLY. SEE SS 668.002 AND FAC 61G15-23.003. | | | | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|