Plan Review Notes
Plan Review Notes For Permit 09040579
Permit Number 09040579
Review Stop B
Sequence Number 2
Notes
Date Text
2009-10-20 11:18:26TRUSS DRAWINGS ARE DENIED
 CORRECTIONS ARE REQUIRED.
  
 1) THE FLOOR TRUSS AND LOWER ROOF LAYOUT SPECIFIES THE
 DESIGN CRITERIA AS FBC 07 / ASCE 7-05 AND EXPOSURE B.
 THE TRUSS DRAWING COVERSHEET SPECIFIES EXPOSURE C. THE
 LOWER ROOF TRUSS DRAWINGS IN THIS PACKAGE SPECIFY ASCE
 7-02 AND EXPOSURE B WITH TCDL OF 5 PSF AND BCDL OF 5
 PSF. PLEASE COORDINATE THE DESIGN CRITERIA AND LOADS
 WITH THE APPROVED PLANS. THE PLANS WERE PERMITTED UNDER
 THE 2004 FBC / ASCE 7-02 AND EXPOSURE B.
  
 NOTE: YOU CAN DESIGN THE TRUSSES USING FBC 2007 AND
 ASCE 7-05, HOWEVER, BECAUSE OF THE CHANGES TO THE
 EXPOSURE CATEGORY DETERMINATIONS IN THE 2009 REVISIONS
 TO FBC 07, THE STRUCTURE IS IN EXPOSURE CATEGORY C
 USING THIS DESIGN CRITERIA.
  
 2) THE TRUSS LAYOUT DRAWINGS ARE REQUIRED TO BE SIGNED
 AND SEALED BY THE TRUSS ENGINEER. THE SIGNATURE ON THE
 TRUSS DRAWING COVER SHEET IS REQUIRED TO BE AN ORIGINAL
 WET SIGNATURE, PHOTO-COPIES, STAMPS, ETC. ARE NOT
 ALLOWED. FAC 61G-15-23.002 AND FS 471. ELECTRONIC
 SIGNATURES OR DIGITAL SIGNATURES ARE ONLY USED FOR
 PLANS OR OTHER DOCUMENTS ARE TRANSMITTED
 ELECTRONICALLY. SEE SS 668.002 AND FAC 61G15-23.003.
  
  