Date Text
2009-06-15 11:07:29REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS COMMENTS FOR THE PURPOSE OF CONTINUITY:
  
 1. PAGE M1.01 SHOWS EF-1 PROVIDING 100 CFM OF EXHAUST
 NEAR THE MANICURE STATION. THIS IS PRESUMED TO BE THE
 EXHAUST REQUIRED FOR THE HAIR AND NAIL SALON AREAS AS
 REQUIRED BY ASHRAE 62.1-2004. TABLE 6-4 REQUIRES A
 MINIMUM VENTILATION RATE OF 0.6 CFM/S.F. EXHAUSTIN THE
 MANICURE, PEDICURE, COLOR AND STYLING AREAS. 100 CFM IS
 NOT ADEQUATE VENTILATION FOR ALL OF THESE AREAS SHOWN
 ON THE PLANS. ALSO, PLEASE PROVIDE EXHAUST IN EACH OF
 THESE AREAS AS REQUIRED IN ACCORDANCE WITH FBC-M
 502.1.1.
  
 2. PAGE M2.02: FLOOR PLAN AND SCHEDULE ARE NOW
 COORDINATED. HOWEVER, PLEASE SEE COMMENT #1 REGARDING
 TOTAL EXHAUST REQUIREMENTS FOR THE PROPOSED SPACES.
  
 3. THIS COMMENT HAS BEEN ADDRESSED. HOWEVER, PLEASE
 CLARIFY PLANS AS PAGE M1.01 CALLS FOR A "GRAVERY"
 DAMPER RATHER THAN A GRAVITY DAMPER. FBC-B
 13-409.AB.3.3.
  
 4. FLOOR PLAN ON M1.01: WRITTEN RESPONSE INDICATES "THE
 SPACE IS NOT PRESSURIZED." THIS IS A PROBLEM AS THE
 CODE SECTION CITED IN PREVIOUS REVIEW (FBC-B
 13-409.AB.2) REQUIRES THE SPACE TO BE PRESSURIZED WITH
 RESPECT TO THE OUTDOORS. THE VENTILATION SYSTEM SHALL
 BE DESIGNED TO ENSURE THE SPACE IS POSITIVELY
 PRESSURIZED, NOT NEUTRAL AS THE WRITTEN RESPONSE AND
 NEW DESIGN INDICATES. WHEN RESPONDING TO THIS COMMENT,
 PLEASE TAKE INTO ACCOUNT THE ADDITIONAL EXHAUST
 REQUIRED TO ADDRESS COMMENT #1 ABOVE.
  
 5. OK
  