| 2009-06-15 11:07:29 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS COMMENTS FOR THE PURPOSE OF CONTINUITY: |
| | |
| | 1. PAGE M1.01 SHOWS EF-1 PROVIDING 100 CFM OF EXHAUST |
| | NEAR THE MANICURE STATION. THIS IS PRESUMED TO BE THE |
| | EXHAUST REQUIRED FOR THE HAIR AND NAIL SALON AREAS AS |
| | REQUIRED BY ASHRAE 62.1-2004. TABLE 6-4 REQUIRES A |
| | MINIMUM VENTILATION RATE OF 0.6 CFM/S.F. EXHAUSTIN THE |
| | MANICURE, PEDICURE, COLOR AND STYLING AREAS. 100 CFM IS |
| | NOT ADEQUATE VENTILATION FOR ALL OF THESE AREAS SHOWN |
| | ON THE PLANS. ALSO, PLEASE PROVIDE EXHAUST IN EACH OF |
| | THESE AREAS AS REQUIRED IN ACCORDANCE WITH FBC-M |
| | 502.1.1. |
| | |
| | 2. PAGE M2.02: FLOOR PLAN AND SCHEDULE ARE NOW |
| | COORDINATED. HOWEVER, PLEASE SEE COMMENT #1 REGARDING |
| | TOTAL EXHAUST REQUIREMENTS FOR THE PROPOSED SPACES. |
| | |
| | 3. THIS COMMENT HAS BEEN ADDRESSED. HOWEVER, PLEASE |
| | CLARIFY PLANS AS PAGE M1.01 CALLS FOR A "GRAVERY" |
| | DAMPER RATHER THAN A GRAVITY DAMPER. FBC-B |
| | 13-409.AB.3.3. |
| | |
| | 4. FLOOR PLAN ON M1.01: WRITTEN RESPONSE INDICATES "THE |
| | SPACE IS NOT PRESSURIZED." THIS IS A PROBLEM AS THE |
| | CODE SECTION CITED IN PREVIOUS REVIEW (FBC-B |
| | 13-409.AB.2) REQUIRES THE SPACE TO BE PRESSURIZED WITH |
| | RESPECT TO THE OUTDOORS. THE VENTILATION SYSTEM SHALL |
| | BE DESIGNED TO ENSURE THE SPACE IS POSITIVELY |
| | PRESSURIZED, NOT NEUTRAL AS THE WRITTEN RESPONSE AND |
| | NEW DESIGN INDICATES. WHEN RESPONDING TO THIS COMMENT, |
| | PLEASE TAKE INTO ACCOUNT THE ADDITIONAL EXHAUST |
| | REQUIRED TO ADDRESS COMMENT #1 ABOVE. |
| | |
| | 5. OK |
| | |