Plan Review Notes
Plan Review Notes For Permit 09040575
Permit Number 09040575
Review Stop P
Sequence Number 1
Notes
Date Text
2009-05-06 16:28:32DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 EXISTING BUILDING
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. SHT A1.03 DETAIL 2/A1.03 THE POWDER ROOM SHALL BE
 ACCESSIBLE PER SECTION 11-4.1.3(11) & 11-4.1.6(1)(B).
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS AS WELL
 AS A FLOOR PLAN SHOWING ALL CLEAR FLOOR SPACES, TURNING
 AREA, DISTANCE OFF THE WALLS TO THE CENTERLINE OF THE
 FIXTURES, (18" FOR W/C, MIN. 15" FOR LAV). FIGURE 28.
  
 2. SHT A1.03 DETAIL 2/A1.03 THE BREAKROOM SINK SHALL BE
 ACCESSIBLE PER SECTION 1104.24. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24 WITH ALL
 SUBSECTIONS. (CLEAR FLOOR SPACE SHALL BE FORWARD
 APPROACH AND CABINET DOORS ARE NOT APPROVED IN THE
 CLEAR FLOOR SPACE). SHOW CLEAR FLOOR SPACE ON THE FLOOR
 PLAN AND SUBMIT AN ELEVATION FOR THE OTHER
 REQUIREMENTS.
  
 3. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE THE LOCATION ON THE FLOOR PLAN AND
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15
 WITH ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 4. SHT P2.01 SANITARY ISOMETRIC RISER DIAGRAM SHOWS AIR
 ADMITTANCE VALVES AT THE SHAMPOO/PEDICURE CHAIRS. PER
 SECTION 917.3.2 A RELIEF VENT IS REQUIRED.
  
 5. SHT P2.01 SANITARY ISOMETRIC RISER DIAGRAM SHOWS
 DOUBLE TRAPS FOR THE SHAMPOO/PEDICURE CHAIRS. THIS IS
 PROHIBITED PER SECTION 1002.1.
  
 6. SHT P201 SANITARY ISOMETRIC RISER DIAGRAM. FLOOR
 DRAINS ARE NOT APPROVED INDIRECT WASTE INTERCEPTORS. A
 FLOOR SINK IS REQUIRED. SECTION 802.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  