2009-05-12 13:42:27REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1.01 SHOWS EF-1 PROVIDING 175 CFM OF EXHAUST.
 THIS IS PRESUMED TO BE THE EXHAUST REQUIRED FOR THE
 HAIR AND NAIL SALON AREAS AS REQUIRED BY ASHRAE
 62.1-2004. THIS INTAKE LOCATION IS VERY REMOTE IN
 RELATION TO THE AREA BEING EXHAUSTED. THE INLET TO THE
 EXHAUST SYSTEM SHALL BE LOCATED IN THE AREA OF HEAVIEST
 CONCENTRATION OF CONTAMINANTS IN ACCORDANCE WITH FBC-M
 502.1.1. ALSO, PLEASE CONFIRM THAT THE ENTIRE AREAS OF
 THE MANICURE STATIONS, PEDICURE STATIONS AND HAIR CARE
 STATIONS ARE BEING USED TO CALCULATE THE REQUIRED
 EXHAUST RATE OF 0.6 CFM/SQ.FT AS REQUIRED BY ASHRAE
 62.1-2004 TABLE 6-4.
  
 2. PAGE M2.02: THE VENTILATION FAN SCHEDULE SHOWS EF-1
 RATED FOR 175 CFM. HOWEVER, THE FLOOR PLAN ON PAGE
 M1.01 SHOWS EF-1 PROVIDING A TOTAL OF 250 CFM FOR TWO
 LOCATIONS (ENTRANCE AREA AND LASER REMOVAL). PLEASE
 COORDINATE EQUIPMENT SCHEDULE AND FLOOR PLANS SHOWING
 THE EQUIPMENT SPECIFIED IS CAPABLE OF PROVIDING THE
 EHAUST RATES CALLED FOR ON THE FLOOR PLAN IN ACCORDANCE
 WITH FBC-M 501.1 AND FBC-M 403.4.
  
 3. PROVIDE MOTORIZED OR GRAVITY OPERATED SHUTOFF DAMPER
 CONTROLS AT FRESH AIR INTAKES IN ACCORDANCE WITH FBC-B
 13-409.AB.3.3.
  
 4. FLOOR PLAN ON M1.01 SHOWS A TOTAL OF 350 CFM OF
 EXHAUST (EF-1 PLUS TWO BATH EXHAUST FANS) WHILE THE
 VENTILATION DESIGN CRITERIA CALLS FOR A TOTAL OF 275
 CFM OF OUTSIDE AIR. THIS WILL CAUSE THIS SPACE TO BE
 OPERATING UNDER AN OVERALL NEGATIVE PRESSURE. THE
 MECHANICAL SYSTEM SHALL BE DESIGNED TO ASSURE THAT THIS
 SPACE IS PRESSURIZED WITH RESPECT TO THE OUTDOORS IN
 ACCORDANCE WITH FBC-B 13-409.AB.2.
  
 5. ENERGY CLACULATIONS SUBMITTED FOR THIS PROJECT ARE
 FORM 400A-2004R. THIS FORM IS NO LONGER VALID AS OF
 MARCH 1, 2009. AS THIS PROJECT DOES NOT LIKELY MEET THE
 DEFINITION OF A RENOVATION (SEE FBC-B 13-101.1.3) SHOW
 COMPLIANCE WITH ENERGY CODE REQUIREMENTS BY SUBMISSION
 OF FORM 400B-08 IN ACCORDANCE WITH FBC-B 13-101.6.
  