| Plan Review Notes For Permit 09040575 |
| Permit Number |
09040575 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-05-06 12:55:20 | *****DENIED***** | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATION SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. THE PLANS LIST THE PROJECT SITE AS UNIT 012 WHEREAS | | | BASED ON A FIELD SITE SURVEY THE UNIT IS LISTED AS 112. | | | PLEASE EXPLAIN AND OR AMEND. BE ADVISED THAT THE ACTUAL | | | SITE LOCATION SHALL BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | 3. THE PROJECT SUMMARY(SHEET 1) INCORRECTLY STATES THE | | | OCCUPANCY AS BEING A RETAIL TYPE, WHEREAS THE BUILIDING | | | OCCUPANCY TYPE LISTED ON SHEET A1.01 REFERS TO THE | | | STRUCTURE AS A BUSINESS TYPE. PLEASE AMEND | | | | | | 4. PROVIDE PRESCRIPTIVE STRENGTH FOR THE NEW GUARDRAILS | | | AND HANDRAILS | | | | | | 5. PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCE | | | TO THE EXIT(S), THE EXIT LIGHT(S), FIRE ALARM DEVICES, | | | EMERGENCY LIGHT(S), AND THE 2A:BC RATED FIRE | | | EXTINGUISHER(S). | | | | | | 6. SPECIFY THE INTERIOR WALL AND CEILING FINISH | | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 7. SPECIFY INTERIOR FLOOR FINISH IN TERMS OF CLASS I, | | | OR CLASS II. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE/HOW THE COMMENTS WERE ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|