Plan Review Notes
Plan Review Notes For Permit 09040557
Permit Number 09040557
Review Stop E
Sequence Number 1
Notes
Date Text
2009-05-18 08:49:37**DENIED REVIEW **
  
 1) NOTE: PLANS SUBMITTED CONTAIN A RUBBER STAMP IN LIEU
 OF THE REQUIRED ORIGINAL SIGNATURE. THIS IS NOT
 PERMITTED PER FS 481.221. THIS ARCHITECT HAS BEEN
 NOTIFIED BY THIS OFFICE ON MORE THAN ONE OCCASION ON
 PREVIOUS PROJECTS OF THIS VIOLATION OF FLORIDA
 STATUTES. ONE SET WILL BE RETAINED BY THIS OFFICE.
 PLANS MAY BE FORWARDED TO THE BOARD OF ARCHITECTS. THIS
 HAS BEEN CONFIRMED WITH THE BOARD OF ARCHITECTS
 ATTORNEY AND INVESTIGATOR.
  
 2) NOTE: PLEASE SEE 250.50 AS THE NEW FOOTER STEEL
 SHALL BE BONDED PART OF THE GROUNDING ELECTRODE SYSTEM.
  
 3) NOTE: PLEASE SUBMIT ELECTRICAL FOR NEW. PLEASE SEE
 210.52G AND 210.8A2 AS A NEW GFI RECEPTACLE IS
 REQUIRED.
  
 4) NOTE: PLEASE INDICATE THE REQUIRED DEDICATED CIRCUIT
 FOR THE GARAGE DOOR OPENER. 240.4, 310.16, 430. 248.
 408.4
  
 5) NOTE: PLEASE CLARIFY THE SCOPE OF WORK ON PLANS.
 THERE ARE ITEMS SUCH AS CONDENSING UNITS, OUTSIDE GFI
 ETC WHICH ARE SHOWN HOWEVER NOT SHOWN AS EXISTING. IF
 ITEMS ARE NOT INDICATED AS EXISTING THEN THEY ARE
 LOOKED AT AS BEING NEW. PLEASE KNOW THIS WOULD AFFECT
 THE REVIEW AND OR COMMENTS.
  
 6) NOTE: PLANS SHALL STATE MINIMUM CODE UNDER PERMIT
 APPLICATION MADE.
 ALL PLANS AFTER MARCH 1ST, 2009 SHALL CONTAIN THE
 FOLLOWING AT A MINIMUM FOR THIS SCOPE.
 2007 FBC W/ 2009 REVISIONS
 2005 NFPA-70
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  