| 2009-05-18 08:49:37 | **DENIED REVIEW ** |
| | |
| | 1) NOTE: PLANS SUBMITTED CONTAIN A RUBBER STAMP IN LIEU |
| | OF THE REQUIRED ORIGINAL SIGNATURE. THIS IS NOT |
| | PERMITTED PER FS 481.221. THIS ARCHITECT HAS BEEN |
| | NOTIFIED BY THIS OFFICE ON MORE THAN ONE OCCASION ON |
| | PREVIOUS PROJECTS OF THIS VIOLATION OF FLORIDA |
| | STATUTES. ONE SET WILL BE RETAINED BY THIS OFFICE. |
| | PLANS MAY BE FORWARDED TO THE BOARD OF ARCHITECTS. THIS |
| | HAS BEEN CONFIRMED WITH THE BOARD OF ARCHITECTS |
| | ATTORNEY AND INVESTIGATOR. |
| | |
| | 2) NOTE: PLEASE SEE 250.50 AS THE NEW FOOTER STEEL |
| | SHALL BE BONDED PART OF THE GROUNDING ELECTRODE SYSTEM. |
| | |
| | 3) NOTE: PLEASE SUBMIT ELECTRICAL FOR NEW. PLEASE SEE |
| | 210.52G AND 210.8A2 AS A NEW GFI RECEPTACLE IS |
| | REQUIRED. |
| | |
| | 4) NOTE: PLEASE INDICATE THE REQUIRED DEDICATED CIRCUIT |
| | FOR THE GARAGE DOOR OPENER. 240.4, 310.16, 430. 248. |
| | 408.4 |
| | |
| | 5) NOTE: PLEASE CLARIFY THE SCOPE OF WORK ON PLANS. |
| | THERE ARE ITEMS SUCH AS CONDENSING UNITS, OUTSIDE GFI |
| | ETC WHICH ARE SHOWN HOWEVER NOT SHOWN AS EXISTING. IF |
| | ITEMS ARE NOT INDICATED AS EXISTING THEN THEY ARE |
| | LOOKED AT AS BEING NEW. PLEASE KNOW THIS WOULD AFFECT |
| | THE REVIEW AND OR COMMENTS. |
| | |
| | 6) NOTE: PLANS SHALL STATE MINIMUM CODE UNDER PERMIT |
| | APPLICATION MADE. |
| | ALL PLANS AFTER MARCH 1ST, 2009 SHALL CONTAIN THE |
| | FOLLOWING AT A MINIMUM FOR THIS SCOPE. |
| | 2007 FBC W/ 2009 REVISIONS |
| | 2005 NFPA-70 |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |