2009-05-08 16:55:15BUILDING PLAN REVIEW
 PERMIT: 09040557
 ADD: 8036 CRANES POINTE WAY
 CONT: SHELDON FRIEFELD, INC.
 TEL: (561)722-5078
  
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009, 2007 EXISTING BUILDING CODE WITH
 2009 SUPPLEMENTS, CHAPTER 10 FOR ADDITIONS.
  
 2) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3) MISSING DESIGN PERIMETERS: 110.2* W. P. B.
 ADMINISTRATIVE CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 4) R301.1.2.1.1 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL, FRONT ELEVATION AND ROOF ZONES.
  
 5) SHEET A3 DETAIL# 1 IS MISSING INFORMATION ON THE
 FOUNDATION, SIZE OF REBAR, PSI OF CONCRETE, DENSITY OF
 SOILS, MINIMUM BEARING VALUE OF SOILS, VAPOR BARRIER
 AND TERMITE TREATMENT INFORMATION. R401.4, R401.4.1,
 R402.2, R405.2.2, R2304.11.6.
  
 6) PRODUCT APPROVALS FOR CAST CRETE LINTELS WAS
 SUBMITTED FOR REVIEW BUT THERE IS NO INDICATION AS TO
 INSTALATION, OVER THE WINDOWS OR GARAGE DOOR, SIZE OF
 LINTAL DEPTH OF LINTAL.
 THE GARAGE OVERHEAD DOOR ALSO IS MISSING INFORMATION IF
 THIS IS TO BE A LINTAL, ACOMBINATION LINTEL AND BOND
 BEAM OR A BEAM WITH REBAR AND STIRRUPS. THE PLANS DO
 NOT INDICATE CHIPPING BACK INTO THE EXISTING CORNER TO
 BEAR THE NEW BEAM OR LINTAL ONTO THE EXISTING COLUMN.
  
 7) PLANS FAIL TO PROVIDE A TRUSS PLAN WITH THE
 MAGNITUDE OF LOADS TO BE RESISTED, GRAVITY, LATERAL &
 UPLIFT, R802.2.9 ROOF TIE-DOWN.
  
 8) SHEET 3 DETAIL # 1 FAILS TO PROVIDE ROOF SHEATHING
 NAILING PATERNS SEE R802.2.3.1.
  
 9) SHEET# 3 DETAIL# 1 FAILS TO PROVIDE CODE COMPLIANCE
 WITH: REQUIRED VENTILATING AREA IS PROVIDED BY
 VENTILATORS LOCATED IN THE UPPER PORTION OF THE SPACE
 TO BE VENTILATED AT LEAST 3 FEET (914 MM) ABOVE THE
 EAVE OR CORNICE VENTS
  
 10) R807.1 ATTIC ACCESS. BUILDINGS WITH COMBUSTIBLE
 CEILING OR ROOF CONSTRUCTION SHALL HAVE AN ATTIC ACCESS
 OPENING TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8
 M2) AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 MORE.
  
 11) ENTEGRA ROOF TILE: PLEASE PROVIDE INFORMATION ON
 WHICH SYSTEM IS TO BE USED TO SECURE THE ROOF TILE,
 CIRCLE SYSTEM. R905.3 CLAY AND CONCRETE TILE. THE
 INSTALLATION OF CLAY AND CONCRETE SHALL BE IN
 ACCORDANCE WITH RECOMMENDATIONS OF FRSA/TRI
 07320.R905.3.7.1 HIP AND RIDGE TILES. HIP AND RIDGE
 TILES SHALL BE INSTALLED IN ACCORDANCE WITH FRSA/TRI
 07320.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved