| Plan Review Notes For Permit 09040550 |
| Permit Number |
09040550 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-27 08:58:17 | RESIDENTIAL (R3) REROOF BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 1- DADE COUNTY NOA 07-0111.03 SUBMITTED FOR FLAT ROOF | | | ASSEMBLY WAS SUPERSEDED BY DADE COUNTY. SEE ATTACHED | | | COPY SHOWING NOA STATUS. PROVIDE CURRENT NOA 07-0730.03 | | | WHICH IS IS THE ONE WHO SUPERSEDES NOA SUBMITTED. | | | | | | 2- SELECTED APPROVED ASSEMBLY HIGHLIGHTED ON SHEET 18 | | | OF 19 IS FOR TILE UNDERLAYMENT. NEED TO SELECT APPROVED | | | ASSEMBLY FOR FLAT ROOFING NOT TILE UNDERLAYMENT. | | | | | | 3- MARK ON PRODUCT APPROVAL SPECIFIC BASE SHEET | | | FASTENING OPTION TO BE INSTALLED. | | | | | | 4- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7. SEE GENERAL LIMITATION #7 ON LAST PAGE | | | OF NOA SUBMITTED. | | | | | | 5- OWES $26.18 FOR UPDATED PERMIT VALUATION AS REQUIRED | | | BY SEC. 108.3 CITY AMENDMENTS TO FBC. | | | | | | 6- ROOF WITH 3:12 PITCH REQUIRES 2 LAYERS OF | | | UNDERLAYMENT. SEC. R905.2.2 OF 2007 FLORIDA RESIDENTIAL | | | CODE. | | | | | | 7- ROOF SHEATHING TO BE RENAILED AT 4" O.C. IN ROOF | | | ZONE 3 AS REQUIRED BY SEC. R803.2.3.1 OF 2007 FLORIDA | | | RESIDENTIAL CODE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|