Plan Review Notes
Plan Review Notes For Permit 09040549
Permit Number 09040549
Review Stop E
Sequence Number 1
Notes
Date Text
2009-05-08 10:24:30 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 210.11(C)(1) SMALL-APPLIANCE BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR
 ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B). ***ONLY
 ONE SMALL APPLIANCE CIRCUIT IS SHOWN ON THE PANEL
 SCHEDULE
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  