| Plan Review Notes For Permit 09040549 |
| Permit Number |
09040549 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-05-08 10:24:30 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} 210.11(C)(1) SMALL-APPLIANCE BRANCH CIRCUITS IN | | | ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY | | | OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE | | | SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR | | | ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B). ***ONLY | | | ONE SMALL APPLIANCE CIRCUIT IS SHOWN ON THE PANEL | | | SCHEDULE | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|