Plan Review Notes
Plan Review Notes For Permit 09040483
Permit Number 09040483
Review Stop E
Sequence Number 1
Notes
Date Text
2009-05-06 09:18:17**DENIED PLANS**
  
  
  
 1) NOTE: ALL WIRING METHODS SHALL MEET NEC 525. PLEASE
 BE SURE TO INCLUDE NOTES ACCORDINGLY.
  
 2) NOTE: PLEASE SHOW LOCATIONS AND TYPE OF FIXTURES FOR
 LIGHTING. PLEASE SHOW THE LOCATIONS FOR EGRESS
 LIGHTING, EMERGENCY LIGHTING AND EXIT LIGHTING PER THE
 NFPA-101 2006 7.8 AND 7.9.
  
 3) NOTE: PLEASE NOTE A MINIMUM OF TWO GROUND RODS WILL
 BE REQUIRED. 250.50, 250.56.
  
 4) NOTE: PLEASE INDICATE ALL GFI RECEPTACLE LOCATIONS
 AND ALL AS GFCI PROTECTED PER 210.8B4
  
 5) NOTE: THE GENERATOR LOCATION SHALL MEET MINIMUM
 CLEARANCES FOR EXHAUST PER NFPA-37. THE PLANS DO NOT
 GIVE CLEARANCE DIMENSIONS HOWEVER BASED ON THE PLAN
 LAYOUT THE LOCATION SHOWN IS TOO CLOSE TO BUILDING,
 VENTS, OPENINGS, A/C EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  