| 2009-05-04 15:22:20 | *****DENIED***** |
| | |
| | 1. PROVIDE AN EXISTING FLOOR PLAN FOR THE PROJECT SITE. |
| | STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241, 2004 |
| | EDITION. |
| | |
| | 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE |
| | (BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND |
| | NFPA 1, UNIFORM FIRE CODE, 2006 EDITION) SHALL BE |
| | REFERENCED. |
| | |
| | 3. IF THE PROJECT SCOPE OF WORK IS TO BE DONE IN UNIT |
| | #1 ONLY OF THE ADDRESSED BUILDING, THE ADDRESS LISTED |
| | IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET SHALL |
| | INCLUDE THE UNIT NUMBER ALSO. |
| | |
| | 4. PLEASE LIST THE EXISTING AS WELL AS THE NEW OCCUPANT |
| | LOAD BASED ON THE CHARACTERISTIC OF THE USE OF THE |
| | SPACE. |
| | |
| | 5. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE WALL |
| | AND CEILING (IN THE BEDROOMS) IN TERMS OF CLASS A, |
| | CLASS B, OR CLASS C. |
| | |
| | 6. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE |
| | EXTINGUISHER. |
| | |
| | 7. ON THE APPROPIATE EXTERIOR ELEVATION, DISPLAY/SHOW |
| | THE NUMERICAL ADDRESS FOR THIS BUILDING. AS PER WEST |
| | PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6" |
| | IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE. THE |
| | INDIVIDUAL DWELLING UNIT NUMBERS SHALL BE NO LESS THAN |
| | 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE. |
| | |
| | 8. ON THE ELECTRICAL PLAN (SHEET 3), SMOKE DETECTORS |
| | ARE SHOWN AS BEING USED IN THE PROJECT SPACE. UNLESS |
| | THESE DEVICES ARE TIED INTO A FIRE ALARM SYSTEM FOR THE |
| | BUILDING, AMEND VERBAGE TO REFLECT THAT SMOKE ALARMS |
| | (SA), WHICH ALERT THE OCCUPANT OF THE SAID DWELLING |
| | UNIT ONLY, ARE TO BE USED. |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE THE COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |