| 2009-05-07 10:22:54 | BUILDING PLAN REVIEW |
| | PERMIT: 09040446 |
| | ADD: 2013 DOCK ST. |
| | CONT: ABALON CONSTRUCTION |
| | TEL: (561)722-3890 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009. THREE UNIT STRUCTURE WILL BE |
| | REVIEWED UNDER THE 2007 FLORIDA BUILDING CODE, 2007 |
| | FLORIDA EXISTING BUILDING CODE W/ 2009 SUPPLEMENTS. |
| | |
| | 1C) 2007 FBC 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| | DETERMINED BY THE BUILDING OFFICIAL. THE PLANS DO NOT |
| | INDICATE WHAT WALLS ARE ORIGINAL OR NEW CONSTRUCTION, |
| | PLEASE IDENTIFY. IN UNITS 2 & 3 THERE IS NO INFORMATION |
| | IF THERE IS NEW WORK, DISCUSSION WITH CORAL KEY DESIGN |
| | INDICATES THERE TO BE NO NEW WORK BUT THE FRONT |
| | ELEVATION INDICATES NEW WINDOWS IN UNIT TWO WHERE THE |
| | HEADERS ARE BEING REPLACED. PLEASE CORRELATE PLANS FOR |
| | CONSISTENCY. |
| | |
| | 1D) CORAL KEY DESIGN CAN ONLY DESIGN A ONE & TWO FAMILY |
| | RESIDENCE AND NOT COMMERCIAL WORK. THE P.E. OF RECORD |
| | FOR THIS PROJECT H. JOHN GRIFFIN SHOULD ONLY HAVE HIS |
| | NAME IN THE TITLE-BLOCK. |
| | 1E)THE STATED DOLLAR VALUE FOR THE SCOPE OF WORK |
| | INDICATED IN THE PLAN DOCUMENT IS TOO LOW. PLEASE |
| | UPDATE VALUE TO INCLUDE LABOR AND MATERIAL TO REFLECT A |
| | FAIR MARKET VALUE. |
| | |
| | W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) UNIT# 1, BEDROOM# 2 INDICATES THE WINDOW TO BE |
| | RELOCATED. FL EXIST. BLDG. CODE 701.2 ALTERATION LEVEL |
| | 1 COMPLIANCE. IN ADDITION TO THE REQUIREMENTS OF THIS |
| | CHAPTER, ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | CHAPTER 6. 606.4 REPLACEMENT OF WINDOWS AND DOORS. THE |
| | REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS, SKYLIGHTS, |
| | OPERATIVE AND INOPERATIVE WINDOWS SHALL BE DESIGNED AND |
| | CONSTRUCTED TO COMPLY WITH CHAPTER 16 OF THE FLORIDA |
| | BUILDING CODE, BUILDING . PLEASE NOTE THE RELOCATED |
| | WINDOW WILL NEED DOCUMENTATION THAT IT MEETS THE |
| | CURRENT WIND PRESSURES. THE OTHER ISSUE IS TO IDENTIFY |
| | THROUGH-OUT THE BUILDING WHICH WINDOWS ARE GOING TO BE |
| | REPLACED. |
| | |
| | 3) SHEET# 2 INDICATES PROPOSED STUCCO, OUR RECORDS |
| | INDICATE THIS TO BE A WOOD FRAME STRUCTURE WITH WOOD |
| | SIDING. PLEASE PROVIDE ADDITIONAL INFORMATION ON THE |
| | APPLICATION OF STUCCO. 2510.1 GENERAL. EXTERIOR AND |
| | INTERIOR CEMENT PLASTER AND LATHING SHALL BE DONE WITH |
| | THE APPROPRIATE MATERIALS. |
| | |
| | 2510.3 INSTALLATION. INSTALLATION OF THESE MATERIALS |
| | SHALL BE IN COMPLIANCE WITH ASTM C 926 AND ASTM C 1063. |
| | 1405.3 FLASHING. FLASHING SHALL BE INSTALLED IN SUCH A |
| | MANNER SO AS TO PREVENT MOISTURE FROM ENTERING THE WALL |
| | OR TO REDIRECT IT TO THE EXTERIOR. FLASHING SHALL BE |
| | INSTALLED AT THE PERIMETERS OF EXTERIOR DOOR AND WINDOW |
| | ASSEMBLIES, PENETRATIONS AND TERMINATIONS OF EXTERIOR |
| | WALL ASSEMBLIES |
| | 1404.2 WATER-RESISTIVE BARRIER. EXTERIOR WALLS OF FRAME |
| | CONSTRUCTION RECEIVING A VENEER SHALL BE PROVIDED WITH |
| | A WATER-RESISTIVE BARRIER. THE WATER-RESISTIVE BARRIER |
| | SHALL BE A MINIMUM OF ONE LAYER OF NO. 15 ASPHALT FELT, |
| | COMPLYING WITH ASTM D 226 FOR TYPE 1 FELT OR OTHER |
| | APPROVED MATERIALS, SHALL BE ATTACHED TO THE SHEATHING, |
| | WITH FLASHING AS DESCRIBED IN SECTION 1405.3, IN SUCH A |
| | MANNER AS TO PROVIDE A CONTINUOUS WATER-RESISTIVE |
| | BARRIER BEHIND THE EXTERIOR WALL VENEER. |
| | |
| | 1404.2.1 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED |
| | TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL BE |
| | TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER AND |
| | THE WATER RESISTIVE BARRIER. A BOND BREAK SHALL BE |
| | PROVIDED BETWEEN THE WATER RESISTIVE BARRIER AND THE |
| | CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE |
| | FOLLOWING: |
| | |
| | 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER OR |
| | |
| | 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER |
| | OVER AN APPROVED PLASTIC HOUSE WRAP, OR |
| | |
| | 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN |
| | ACCORDANCE WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |
| | |
| | |