| Plan Review Notes For Permit 09040427 |
| Permit Number |
09040427 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-06-03 16:14:56 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | COMMENT FROM PREVIOUS LIST: | | | | | | 2. DESIGN PRESSURE APPEARS TOO LOW (+-35PSF). THIS IS A | | | HIGH RISE BUILDING LOCATED IN EXPOSURE C. PROVIDE | | | ENGINEERING FOR DESIGN PRESSURES FOR THIS OPENING, | | | FBC1609. | | | | | | 2ND REVIEW, ENGINEERING NOT PROVIDED. ALSO SEE NEW | | | COMMENT | | | | | | 3. THIS IS A COMMERCIAL BUILDING; IS ANY FIRE | | | RESISTANCE RATING REQUIRED? HOW HAS THIS BEEN | | | DETERMINED? FBC CHAPTER 6, 7. | | | | | | NOT ADDRESSED OTHER THAN CONTRACTOR'S NOT "NOT | | | REQUIRED." | | | | | | NEW COMMENT: | | | | | | PROVIDE A LOCATION PLAN SHOWING DOOR LOCATIONS. IT IS | | | NOT CLEAR WHETHER THESE DOORS WILL BE INSTALLED IN ZONE | | | 4 OR ZONE 5, FBC16. APPLICATION STATES "DOUBLE DOOR | | | SYSTEM TO MEET WIND LOAD." PLEASE CLARIFY WHAT THIS | | | MEANS. BASED ON PAPERWORK PROVIDED, IT APPEARS THAT TWO | | | DOORS WILL BE INSTALLED. | | | | | | | | | (NOTE - CALLED CONTRACTOR; CONTR HAS ENGINEERING TO | | | CLARIFY ALL ISSUES, WILL PROVIDE WITH THE RESUBMITTAL) | | | |
|