| 2009-04-21 14:12:35 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. PROVIDE ENGINEERING TO JUSTIFY PROPOSED DESIGN |
| | PRESSURES, FBC 1609. (+30S/-50S). |
| | |
| | 2. PLEASE PROVIDE CERTIFICATION FOR THE BUILDING |
| | HEIGHT. YOU AHVE DECLARED A BUILDING HEIGHT OF 96 FEET; |
| | PAPA SHOWS THIS TO BE A 20+STORY BUILDING. OTHER |
| | CONTRACTORS STATE THAT THIS IS A 200' BUILDING. |
| | |
| | 3. PLEASE COMPLETE THE INSTALLATION SCHEDULE. ANCHOR |
| | SPACING HAD "NOA" WRITTEN IN THAT COLUMN. THIS SHOULD |
| | BE THE ANCHOR SPACING IN INCHES PROPOSED. IT APPEARS |
| | THAT YOU PROPOSE 3.8". |
| | |
| | 4. PLEASE COMPLETE THE COLUMN "SHUTTER MOUNTING |
| | CONNECTION TYPE." IT APPEARS THAT YOU PROPOSE TO USE |
| | AA. |
| | |
| | 5. IF AA IS USED, TAPCON, MINIMUM EDGE DISTANCE |
| | IREQUIRED IS 3 1/8". PLEASE REVISE INSTALLATION |
| | SCHEDULE (2" PROPOSED; DOES NOT COMPLY WITH PRODUCT |
| | APPROVAL). |
| | |
| | 6. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72. THE PRODUCT APPROVAL FOR ROLLER STAR IS |
| | "VALIDATED," SHOULD SAY "APPROVED." |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | |
| | |
| | |