Plan Review Notes
Plan Review Notes For Permit 09040407
Permit Number 09040407
Review Stop M
Sequence Number 2
Notes
Date Text
2009-10-17 11:28:17**PROVISO**
  
 THE FOLLOWING CONDITIONS ARE TO BE ADDRESSED IN THE
 FIELD. NO FURTHER REVISIONS REQUIRED IF WORK IS
 COMPLETED PER THE STAMPED PLANS.
  
 1. DRYER EXHAUST DUCT PENETRATION AT SHAFT ENCLOSURE
 SHALL BE PROTECTED WITH A THROUGH-PENETRATION FIRESTOP
 SYSTEM IN ACCORDANCE WITH FBC-M 607.1.1.
  
 2. EF-2 AND EF-3 ABOVE HARD CEILINGS SHALL BE
 ACCESSIBLE FOR SERVICE OR REPLACEMENT IN ACCORDANCE
 WITH FBC-M 306.1.
  