| 2009-04-30 09:52:26 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | NOTE: THE PLANS SUBMITTED WERE ORIGINALLY FOR EXPIRED |
| | PERMIT #06070806. AS THE PREVIOUS PERMIT HAS EXPIRED, |
| | THE PROPOSED WORK IS NOW SUBJECT TO THE REQUIREMENTS OF |
| | THE CODE IN EFFECT AT TIME OF NEW PERMIT APPLICATION. |
| | THE 2007 FLORIDA BUILDING CODE WITH 2009 SUPPLEMENT IS |
| | IN EFFECT AS OF MARCH 1, 2009. THESE PLANS ARE3 BEING |
| | REVIEWED FOR COMPLIANCE WITH THE NEW CODE. |
| | |
| | 1. PAGE M100 SHOWS SEVERAL NEW DUCT PENETRATIONS OF |
| | EXISTING SHAFT ENCLOSURES. PLEASE SHOW HOW THESE DUCT |
| | PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH |
| | FBC-EB 703.2.1. |
| | |
| | 2. PAGE M100 SHOWS NEW KITCHEN AND DRYER EXHAUST DUCTS |
| | BEING INSTALLED IN THE CEILING PLENUM AREA. EXHAUST |
| | DUCTS UNDER POSITIVE PRESSURE SHALL NOT EXTEND INTO OR |
| | PASS THROUGH A PLENUM IN ACCORDANCE WITH FBC-M 601.5. |
| | |
| | 3. PAGE M100 (PHOTOCOPY OF PREVIOUS PERMIT SET) |
| | CONTAINS HAND-WRITTEN NOTES FROM FIELD INSPECTOR |
| | IDENTIFYING WORK WHICH WAS DONE CONTRARY TO THE |
| | APPROVED PLANS. WORK SHALL BE INSTALLED IN ACCORDANCE |
| | WITH THE APPROVED CONSTRUCTION DOCUMENTS, AND ANY |
| | CHANGES MADE DURING CONSTRUCTION THAT ARE NOT IN |
| | COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS |
| | SHALL BE RESUBMITTED FOR APPROVAL AS AN AMENDED SET OF |
| | CONSTRUCTION DOCUMENTS IN ACCORDANCE WITH FBC-B 106.4. |
| | PLEASE REVISE PLANS TO REFLECT THE WORK WHICH WAS NOT |
| | DONE IN ACCORDANCE WITH THE PREVIOUS PLANS. |
| | |