Plan Review Notes For Permit 09040407
Permit Number 09040407
Review Stop M
Sequence Number 1
Notes
Date Text
2009-04-30 09:52:26REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: THE PLANS SUBMITTED WERE ORIGINALLY FOR EXPIRED
 PERMIT #06070806. AS THE PREVIOUS PERMIT HAS EXPIRED,
 THE PROPOSED WORK IS NOW SUBJECT TO THE REQUIREMENTS OF
 THE CODE IN EFFECT AT TIME OF NEW PERMIT APPLICATION.
 THE 2007 FLORIDA BUILDING CODE WITH 2009 SUPPLEMENT IS
 IN EFFECT AS OF MARCH 1, 2009. THESE PLANS ARE3 BEING
 REVIEWED FOR COMPLIANCE WITH THE NEW CODE.
  
 1. PAGE M100 SHOWS SEVERAL NEW DUCT PENETRATIONS OF
 EXISTING SHAFT ENCLOSURES. PLEASE SHOW HOW THESE DUCT
 PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH
 FBC-EB 703.2.1.
  
 2. PAGE M100 SHOWS NEW KITCHEN AND DRYER EXHAUST DUCTS
 BEING INSTALLED IN THE CEILING PLENUM AREA. EXHAUST
 DUCTS UNDER POSITIVE PRESSURE SHALL NOT EXTEND INTO OR
 PASS THROUGH A PLENUM IN ACCORDANCE WITH FBC-M 601.5.
  
 3. PAGE M100 (PHOTOCOPY OF PREVIOUS PERMIT SET)
 CONTAINS HAND-WRITTEN NOTES FROM FIELD INSPECTOR
 IDENTIFYING WORK WHICH WAS DONE CONTRARY TO THE
 APPROVED PLANS. WORK SHALL BE INSTALLED IN ACCORDANCE
 WITH THE APPROVED CONSTRUCTION DOCUMENTS, AND ANY
 CHANGES MADE DURING CONSTRUCTION THAT ARE NOT IN
 COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS
 SHALL BE RESUBMITTED FOR APPROVAL AS AN AMENDED SET OF
 CONSTRUCTION DOCUMENTS IN ACCORDANCE WITH FBC-B 106.4.
 PLEASE REVISE PLANS TO REFLECT THE WORK WHICH WAS NOT
 DONE IN ACCORDANCE WITH THE PREVIOUS PLANS.
  