| 2009-05-01 12:21:25 | *****DENIED***** |
| | |
| | THE FOLLOWING FIRE PLAN REVIEW WAS CONDUCTED BASED ON |
| | THE SUBMITTED PLAN SHEETS; HOWEVER THESE SHEETS ARE |
| | COPIES WHICH WERE PREVIOUSLY SIGNED AND SEALED (PLEASE |
| | SEE OTHER PLAN EXAMINERS' COMMENT(S) IN REFERENCE TO |
| | THIS MATTER) |
| | |
| | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 2. THE ADDRESS IN THE TITLE BLOCK OF EACH SUBMITTED |
| | PLAN INDICATES THE PROJECT SITE AS PENTHOUSE 1E & |
| | CABANA 41. HOW DOES THAT CORRELATE WITH SUITE 30E AS |
| | LISTED ON THE PERMIT APPLICATION AND/OR IN THE CITY'S |
| | PERMITTING SYSTEM. PLEASE BE ADVISED THAT THE ACTUAL |
| | PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK OF |
| | EACH SUBMITTED PLAN SHEET. |
| | |
| | 3. THE SUBMITTED PLAN SHEETS MEP-1 THRU P-101 HAVE NO |
| | PROJECT SITE ADDRESS. PLEASE BE ADVISED THAT THE ACTUAL |
| | PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK OF |
| | EACH SUBMITTED PLAN SHEET. |
| | |
| | 4. AS OF DECEMBER 31ST 2008, THE 2007 EDITION OF |
| | FLORIDA FIRE PREVENTION CODE (BASED ON NFPA 101, LIFE |
| | SAFETY CODE, 2006 EDITION AND NFPA 1, UNIFORM FIRE |
| | CODE, 2006 EDITION) SHALL BE REFERENCED. |
| | |
| | 5. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW |
| | WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR |
| | CLASS C. |
| | |
| | 6. SHOW THE LOCATION OF THE SMOKE ALARMS (SA) FOR THIS |
| | PROJECT SITE. UNSURE IF THESE DEVICES ARE THE SAME AS |
| | THOSE LISTED AS FIRE ALARM LISTED ON SHEET R-100 IN THE |
| | SYMBOLS LEGEND. |
| | |
| | 7. UNABLE TO DIFFERENTIATE BETWEEN FIRE ALARM AND |
| | DECORATIVE PENDANT/SCONCE SURFACE MOUNTED LIGHT AS |
| | LISTED ON SHEET R-100 IN THE SYMBOLS LEGEND. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE/HOW EACH COMMENT WAS ADDRESSED |
| | |
| | |