| 2009-04-17 17:23:59 | RESIDENTIAL (R3) RE-ROOFING, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 1- NOA 06-0601.08 SUBMITTED DOESN'T CORRESPOND TO |
| | FLORIDA PRODUCT APPROVAL FL735-R3 SUBMITTED. SUBMIT NOA |
| | ALONE OR PROVIDE NOA THAT IS LISTED ON THE FLORIDA |
| | PRODUCT APPROVAL FL 735-R3. |
| | |
| | 2- CLARIFY IF EXISTING ROOF IS A CONCRETE DECK. NOA |
| | SUBMITTED IS FOR CONCRETE DECK APPLICATIONS. |
| | |
| | 3- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO |
| | BE INSTALLED. ALSO, INDICATE WHICH BASE SHEET FASTENING |
| | OPTION IS GOING TO BE USED. TO VERIFY THE UPLIFT |
| | PRESSURES AS REQUIRED BY SEC. R301 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | ***NOTE: IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR PERIMETER AND CORNER ROOF AREAS AS |
| | REQUIRED BY TABLE R301.2(2) OF 2007 FLORIDA RESIDENTIAL |
| | CODE AND SELECTED ASSEMBLY IS LIMITED BY GENERAL |
| | LIMITATION #7, THEN RAS 117 CALCULATIONS NEED TO BE |
| | PROVIDED. ACCORDING TO NOA SUBMITTED RAS 117 |
| | CALCULATIONS NEED TO BE SIGNED AND SEALED AS REQUIRED |
| | BY GENERAL LIMITATION #7. SEE GENERAL LIMITATION #7 ON |
| | LAST PAGE OF NOA SUBMITTED. |
| | ON THE OTHER HAND, IF SELECTED ASSEMBLY IS LIMITED BY |
| | GENERAL LIMITATION #9, THEN RAS 117 CALCULATIONS CAN'T |
| | BE PROVIDED IF THE SELECTED ASSEMBLY DOESN'T MEET THE |
| | DESIGN PRESSURES. SEE GENERAL LIMITATION #9 ON LAST |
| | PAGE OF NOA SUBMITTED. |
| | NOTE: SEE ATTACHED COPY OF CITY POLICY FOR RE-ROOFING |
| | PERMITS. |
| | |
| | 4- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |