| Date |
Text |
| 2009-06-18 15:30:07 | |
| | ** DENIED PLANS * |
| | |
| | 1) NOTE: PLANS CONTAIN SEVERAL ITEMS HAND DRAWN ON |
| | SHEETS WHICH ARE ALREADY SIGNED, DATED AND SEALED BY |
| | THE ARCHITECT. THIS IS NOT PERMITTED PER FS 481.221. |
| | PLEASE HAVE SHEETS REVISED BY THE ARCHITECT, SIGNED, |
| | DATED AND SEALED WITH THE RAISED SEAL. |
| | |
| | 2) NOTE: PLEASE COORDINATE CIRCUITING FOR SMOKE ALARMS. |
| | THE PANEL SCHEDULE INDICATES THE SMOKE ALARMS ON |
| | DEDICATE BATH CIRCUITED WHICH IS NOT PERMITTED. THE |
| | PANEL SCHEDULE ALSO INDICATES THE SMOKE ALARMS ON THE |
| | CIRCUIT WITH ONE OF THE BEDROOMS. |
| | ** SMOKE ALARMS REQUIRED TO BE ON AN ARC FAULT |
| | PROTECTED CIRCUIT. SMOKE ALARMS ARE REQUIRED TO BE |
| | INTERCONNECTED WHICH WOULD MEAN THESE WOULD ALL BE ON |
| | THE SAME AFCI PROTECTED CIRCUIT. (NOT ON BATH PER |
| | 210.11C3). |
| | |
| | 3) NOTE: PLEASE PROVIDE LAYOUT OF EXISTING DWELLING |
| | SHOWING NEW OR EXISTING SMOKE ALARMS MEETING CURRENT |
| | NFPA-72. PLEASE KNOW THAT PER FS 553.885 IF THE HOUSE |
| | HAS AN ATTACHED GARAGE OR GAS APPLIANCES ONE CARBON |
| | MONOXIDE DETECTORS ARE REQUIRED. A SMOKE ALARM DEVICE |
| | CAN BE A COMBINATION DEVICE. |
| | 11.8.3, 11.5.1.1, FBC R313.1 |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |