2009-05-01 10:40:13REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE UPDATE PLANS TO REFERENCE THE CORRECT EDITION
 OF THE FLORIDA BUILDING CODE AS WELL AS ALL REFERENCED
 CODE SECTIONS. THE 2007 FLORIDA BUILDING CODE WITH 2009
 SUPPLEMENT IS IN EFFECT AS OF MARCH 1, 2009.
  
 2. PLANS HAVE A NOTE WITH AN OPTION FOR BATH EXHAUST TO
 BE TERMINATED AT THE SOFFIT. BATHROOM EXHAUST SHALL NOT
 TERMINATE IN A SOFFIT IN ACCORDANCE WITH FBC-R SECTION
 M1501.1.
  
 3. PLAN SHOWS THE MAIN RETURN FOR THE AHU LOCATED IN
 THE KITCHEN. THE KITCHEN IS A PROHIBITED SOURCE OF
 RETURN AIR IN ACCORDANCE WITH FBC-R SECTION M1602.2.
 THE RETURN AIR INTAKE MUST BE LOCATED IN AN AREA OF THE
 HOUSE NOT LISTED AS PROHIBITED UNDER THIS SECTION.
  
 4. ONLY PAGE 1 OF THE FORM 1100-08 ENERGY CODE
 COMPLIANCE FORM WAS SUBMITTED. PLEASE PROVIDE A
 COMPLETE FORM (2 SETS ENERGY AND COOLING LOAD) FOR
 REVIEW.
  