| Plan Review Notes For Permit 09040357 |
| Permit Number |
09040357 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-05-01 10:40:13 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PLEASE UPDATE PLANS TO REFERENCE THE CORRECT EDITION | | | OF THE FLORIDA BUILDING CODE AS WELL AS ALL REFERENCED | | | CODE SECTIONS. THE 2007 FLORIDA BUILDING CODE WITH 2009 | | | SUPPLEMENT IS IN EFFECT AS OF MARCH 1, 2009. | | | | | | 2. PLANS HAVE A NOTE WITH AN OPTION FOR BATH EXHAUST TO | | | BE TERMINATED AT THE SOFFIT. BATHROOM EXHAUST SHALL NOT | | | TERMINATE IN A SOFFIT IN ACCORDANCE WITH FBC-R SECTION | | | M1501.1. | | | | | | 3. PLAN SHOWS THE MAIN RETURN FOR THE AHU LOCATED IN | | | THE KITCHEN. THE KITCHEN IS A PROHIBITED SOURCE OF | | | RETURN AIR IN ACCORDANCE WITH FBC-R SECTION M1602.2. | | | THE RETURN AIR INTAKE MUST BE LOCATED IN AN AREA OF THE | | | HOUSE NOT LISTED AS PROHIBITED UNDER THIS SECTION. | | | | | | 4. ONLY PAGE 1 OF THE FORM 1100-08 ENERGY CODE | | | COMPLIANCE FORM WAS SUBMITTED. PLEASE PROVIDE A | | | COMPLETE FORM (2 SETS ENERGY AND COOLING LOAD) FOR | | | REVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|