| 2009-04-28 11:56:20 | **DENIED PLANS** |
| | |
| | ** THE MOST IMPORTANT COMMENT IS IF THERE ARE COMMENTS |
| | WHICH ARE NOT UNDERSTOOD OR TYPED IN A MANNER WHICH IS |
| | NOT CLEAR THEN PLEASE CALL THE REVIEWER. THIS WILL |
| | GREATLY HELP WITH RESOLVING MANY ISSUES WHICH MAY DELAY |
| | ANY PROJECT. |
| | |
| | |
| | 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION AFTER |
| | MARCH 1ST, 2009 SHALL BE UNDER THE DESIGN OF THE 2007 |
| | FBC WITH 2009 AMENDMENTS. |
| | |
| | 2007 FBC W/ 2009 REVISIONS. |
| | 2005 NFPA-70 |
| | |
| | PLEASE ADJUST NOTES. |
| | |
| | 2) NOTE: PLEASE PROVIDE INFORMATION ON SMOKE |
| | ALARMS/DETECTORS PER FBC R313 AND NFPA-72 11.5.1. |
| | PLEASE SHOW ALL EXISTING OR NEW SMOKE ALARMS AS |
| | REQUIRED. |
| | PLANS MAKE REFERENCE TO SMOKE DETECTORS HOWEVER THESE |
| | ARE DEVICES WHICH ONLY DETECT AND DO NOT SOUND AN |
| | ALARM. IN THIS CASE PLEASE INDICATE THE LOW VOLTAGE |
| | FIRE ALARM PANEL AND SOUNDING DEVICES. IF THESE ARE |
| | MEANT TO BE DEVICES WHICH DETECT AND SOUND AN ALARM |
| | THEN THESE WOULD BE SMOKE ALARMS. |
| | PLEASE ADJUST PLANS ACCORDINGLY. |
| | |
| | CIRCUITS ON PANEL SCHEDULE INDICATE TWO CIRCUITS; |
| | HOWEVER AS DEVICES NEED TO BE INTERCONNECTED THEN THESE |
| | MAY NOT BE ON MORE THAN ONE CIRCUIT. |
| | |
| | ** PLEASE ALSO SEE NFPA-72 118.3 AS THE LOCATIONS OF |
| | SMOKE ALARMS/DETECTORS NEED TO COMPLY WITH INSTALLATION |
| | LOCATIONS WITHIN TRAY CEILING AREAS. |
| | |
| | 3) NOTE: PLEASE REVISE PANEL SCHEDULE TO SHOW ALL |
| | CONDUCTORS, CIRCUITS AND OVER CURRENT PROTECTION |
| | DEVICES IN COMPLIANCE WITH THE MINIMUM NEC. |
| | 240.4,310.16, 240.6, 408.4 ETC |
| | PLEASE SEE ITEMS SUCH AS SPRINKLE PUMP WHICH INDICATES |
| | 2-POLE 10AMP BREAKER WITH #6 CONDUCTOR. THIS IS NOT |
| | POSSIBLE NOR CODE COMPLIANT. |
| | PLEASE SEE THERE ARE OTHER ITEMS SUCH AS THE PANEL |
| | SCHEDULE INDICATING A 34 CIRCUIT PANEL. THIS IS NOT A |
| | STANDARD PANEL. 110.3 |
| | PLEASE SEE LOAD NOTES WHICH STATE A 250AMP PANEL IS |
| | RECOMMENDED HOWEVER THE PANEL SHOWN IS A 200AMP PANEL. |
| | PLEASE SUBMIT A RISER DIAGRAM SHOWING THE FEEDERS AND |
| | OVER CURRENT PROTECTION. THE FACT THE PLANS STATES IT |
| | IS A 200AMP PANEL DOES NOT MEAN THE FEEDERS AND OVER |
| | CURRENT PROTECTION FEEDING THIS PANEL IS THE |
| | SAME.215.5, 240.4, 230 ETC |
| | |
| | 4) NOTE: THERE ARE UNDER CABINET LIGHTS WHICH DO NOT |
| | INDICATE ANY CONTROLS. |
| | FBC 106.1.1 FOR CLARITY AND DETAIL OF DOCUMENTS. |
| | 210.70, 300,404 |
| | |
| | 5) NOTE: PLANS INDICATE NEW CABINETS, LAYOUT OF |
| | KITCHEN, LIGHTS ETC HOWEVER NO RECEPTACLES PER |
| | 210.52C1-5 ARE SHOWN. |
| | PLEASE ALSO SEE 210.8A6 FOR REQUIRED GFCI PROTECTION. |
| | |
| | 6) NOTE: PLEASE SHOW THE DISCONNECT FOR AHU, |
| | 440.11,440.14 |
| | |
| | 7) NOTE: PLEASE SEE 408.4 OF THE 2005 NEC. PANEL |
| | SCHEDULES NEED TO BE SPECIFIC TO ALL ROOMS AND AREAS IN |
| | WHICH THEY FEED. STATING GENERAL LIGHTS OR GENERAL |
| | RECEPTACLES IS NOT PERMITTED. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |