Plan Review Notes
Plan Review Notes For Permit 09040357
Permit Number 09040357
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-28 11:56:20**DENIED PLANS**
  
 ** THE MOST IMPORTANT COMMENT IS IF THERE ARE COMMENTS
 WHICH ARE NOT UNDERSTOOD OR TYPED IN A MANNER WHICH IS
 NOT CLEAR THEN PLEASE CALL THE REVIEWER. THIS WILL
 GREATLY HELP WITH RESOLVING MANY ISSUES WHICH MAY DELAY
 ANY PROJECT.
  
  
 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION AFTER
 MARCH 1ST, 2009 SHALL BE UNDER THE DESIGN OF THE 2007
 FBC WITH 2009 AMENDMENTS.
  
 2007 FBC W/ 2009 REVISIONS.
 2005 NFPA-70
  
 PLEASE ADJUST NOTES.
  
 2) NOTE: PLEASE PROVIDE INFORMATION ON SMOKE
 ALARMS/DETECTORS PER FBC R313 AND NFPA-72 11.5.1.
 PLEASE SHOW ALL EXISTING OR NEW SMOKE ALARMS AS
 REQUIRED.
 PLANS MAKE REFERENCE TO SMOKE DETECTORS HOWEVER THESE
 ARE DEVICES WHICH ONLY DETECT AND DO NOT SOUND AN
 ALARM. IN THIS CASE PLEASE INDICATE THE LOW VOLTAGE
 FIRE ALARM PANEL AND SOUNDING DEVICES. IF THESE ARE
 MEANT TO BE DEVICES WHICH DETECT AND SOUND AN ALARM
 THEN THESE WOULD BE SMOKE ALARMS.
 PLEASE ADJUST PLANS ACCORDINGLY.
  
 CIRCUITS ON PANEL SCHEDULE INDICATE TWO CIRCUITS;
 HOWEVER AS DEVICES NEED TO BE INTERCONNECTED THEN THESE
 MAY NOT BE ON MORE THAN ONE CIRCUIT.
  
 ** PLEASE ALSO SEE NFPA-72 118.3 AS THE LOCATIONS OF
 SMOKE ALARMS/DETECTORS NEED TO COMPLY WITH INSTALLATION
 LOCATIONS WITHIN TRAY CEILING AREAS.
  
 3) NOTE: PLEASE REVISE PANEL SCHEDULE TO SHOW ALL
 CONDUCTORS, CIRCUITS AND OVER CURRENT PROTECTION
 DEVICES IN COMPLIANCE WITH THE MINIMUM NEC.
 240.4,310.16, 240.6, 408.4 ETC
 PLEASE SEE ITEMS SUCH AS SPRINKLE PUMP WHICH INDICATES
 2-POLE 10AMP BREAKER WITH #6 CONDUCTOR. THIS IS NOT
 POSSIBLE NOR CODE COMPLIANT.
 PLEASE SEE THERE ARE OTHER ITEMS SUCH AS THE PANEL
 SCHEDULE INDICATING A 34 CIRCUIT PANEL. THIS IS NOT A
 STANDARD PANEL. 110.3
 PLEASE SEE LOAD NOTES WHICH STATE A 250AMP PANEL IS
 RECOMMENDED HOWEVER THE PANEL SHOWN IS A 200AMP PANEL.
 PLEASE SUBMIT A RISER DIAGRAM SHOWING THE FEEDERS AND
 OVER CURRENT PROTECTION. THE FACT THE PLANS STATES IT
 IS A 200AMP PANEL DOES NOT MEAN THE FEEDERS AND OVER
 CURRENT PROTECTION FEEDING THIS PANEL IS THE
 SAME.215.5, 240.4, 230 ETC
  
 4) NOTE: THERE ARE UNDER CABINET LIGHTS WHICH DO NOT
 INDICATE ANY CONTROLS.
 FBC 106.1.1 FOR CLARITY AND DETAIL OF DOCUMENTS.
 210.70, 300,404
  
 5) NOTE: PLANS INDICATE NEW CABINETS, LAYOUT OF
 KITCHEN, LIGHTS ETC HOWEVER NO RECEPTACLES PER
 210.52C1-5 ARE SHOWN.
 PLEASE ALSO SEE 210.8A6 FOR REQUIRED GFCI PROTECTION.
  
 6) NOTE: PLEASE SHOW THE DISCONNECT FOR AHU,
 440.11,440.14
  
 7) NOTE: PLEASE SEE 408.4 OF THE 2005 NEC. PANEL
 SCHEDULES NEED TO BE SPECIFIC TO ALL ROOMS AND AREAS IN
 WHICH THEY FEED. STATING GENERAL LIGHTS OR GENERAL
 RECEPTACLES IS NOT PERMITTED.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  