| 2009-06-03 08:31:52 | BUILDING PLAN REVIEW |
| | PERMIT: 09040336 |
| | ADD: 700 S ROSEMARY# 208 |
| | CONT: SISCA |
| | TEL: (561)248-9041 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | JUNE 03/2009 |
| | 3RD REVIEW |
| | ACTION: REVIEWED |
| | |
| | 1) THIS BUILDING IS A 5 STORY BUILDING (PARKING GARAGE |
| | PORTION) WHICH ENACTS THE FLORIDA STATE THRESHOLD LAWS: |
| | BUILDING CLASSIFICATION AS A BUILDING TYPE: I-B/ A2 |
| | OCCUPANCY |
| | |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | |
| | 1B) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 1C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 09040336 |
| | ADD: 700 S ROSEMARY# 208 |
| | CONT: SISCA |
| | TEL: (561)248-9041 |
| | |
| | BUILDING PROVISO: |
| | THESE FINISH MATERIAL REQUIREMENTS MUST BE MET BEFORE A |
| | CERTIFICATE OF COMPLETION CAN BE ISSUED. |
| | |
| | 1) 803.6 TEXTILES. WHERE USED AS INTERIOR WALL OR |
| | CEILING FINISH MATERIALS, TEXTILES, INCLUDING MATERIALS |
| | HAVING WOVEN OR NONWOVEN, NAPPED, TUFTED, LOOPED OR |
| | SIMILAR SURFACE AND CARPET AND SIMILAR TEXTILE |
| | MATERIALS, SHALL COMPLY WITH THE REQUIREMENTS OF |
| | SECTION 803.6.1, 803.6.2 OR 803.6.3. |
| | |
| | 803.6.1 SURFACE BURNING CHARACTERISTIC TEST. TEXTILE |
| | WALL AND CEILING COVERINGS SHALL HAVE A CLASS A FLAME |
| | SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 AND BE |
| | PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2. |
| | |
| | 803.6.2 ROOM CORNER TEST, TEXTILES. TEXTILE WALL |
| | COVERINGS SHALL MEET THE CRITERIA OF SECTION 803.6.2.1 |
| | WHEN TESTED IN THE MANNER INTENDED FOR USE IN |
| | ACCORDANCE WITH THE METHOD B PROTOCOL OF NFPA 265 USING |
| | THE PRODUCT-MOUNTING SYSTEM, INCLUDING ADHESIVE. |
| | |
| | 803.6.2.1 METHOD B TEST PROTOCOL. DURING THE 40 KW |
| | EXPOSURE, THE INTERIOR FINISH SHALL COMPLY WITH ITEM 1. |
| | DURING THE 150 KW EXPOSURE, THE INTERIOR FINISH SHALL |
| | COMPLY WITH ITEM 2. DURING THE ENTIRE TEST, THE |
| | INTERIOR FINISH SHALL COMPLY WITH ITEM 3. |
| | |
| | 1. DURING THE 40 KW EXPOSURE, FLAMES SHALL NOT SPREAD |
| | TO THE CEILING. |
| | |
| | 2. DURING THE 150 KW EXPOSURE, THE INTERIOR FINISH |
| | SHALL COMPLY WITH THE FOLLOWING: |
| | |
| | 2.1. FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITIES OF |
| | THE SAMPLES ON THE 8-FOOT BY 12-FOOT (203 MM BY 305 MM) |
| | WALLS. |
| | |
| | 2.2. FLASHOVER, AS DESCRIBED IN NFPA 265, SHALL NOT |
| | OCCUR. |
| | |
| | 3. THE TOTAL SMOKE RELEASED THROUGHOUT THE NFPA 265 |
| | TEST SHALL NOT EXCEED 1000 M2. |
| | |
| | 803.6.3 ROOM CORNER TEST, CEILING AND WALL FINISH. |
| | TEXTILE WALL AND CEILING COVERINGS SHALL MEET THE |
| | CRITERIA OF SECTION 803.2.1 WHEN TESTED IN THE MANNER |
| | INTENDED FOR USE IN ACCORDANCE WITH NFPA 286 USING THE |
| | PRODUCT-MOUNTING SYSTEM, INCLUDING ADHESIVE. |
| | |
| | 2) FIBERGLASS LIGHT PANELS: |
| | 2611.1 GENERAL. LIGHT-TRANSMITTING PLASTIC INTERIOR |
| | WALL SIGNS SHALL BE LIMITED AS SPECIFIED IN SECTIONS |
| | 2611.2 THROUGH 2611.4. LIGHT-TRANSMITTING PLASTIC |
| | INTERIOR SIGNS SHALL ALSO COMPLY WITH SECTION 2606. |
| | |
| | 2611.2 AGGREGATE AREA. THE SIGN SHALL NOT EXCEED 20 |
| | PERCENT OF THE WALL AREA. |
| | |
| | 2611.3 MAXIMUM AREA. THE SIGN SHALL NOT EXCEED 24 |
| | SQUARE FEET (2.23 M2). |
| | |
| | 2611.4 ENCASEMENT. EDGES AND BACKS OF THE SIGN SHALL BE |
| | FULLY ENCASED IN METAL. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |