| Plan Review Notes For Permit 09040336 |
| Permit Number |
09040336 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-05-14 15:34:40 | *****UNSAT**** | | | | | | *PREVIOUS COMMENTS WHICH STILL NEED TO BE ADDRESSED: | | | | | | 1. OK | | | | | | 2. ON THE APPROPIATE EXTERIOR ELEVATION (SEE SHEET | | | 1.3A), SHOW DISPLAY THE SUITE NUMBER THIS LOCATION. AS | | | PER WEST PALM BEACH CODE, SUITE NUMBERS SHALL BE NO | | | LESS THAN 3" IN HEIGHT AND NO LESS THAN 1" IN | | | WIDTH/STROKE. | | | | | | 3. EXIT LIGHTS AND EMERGENCY LIGHTS DO NOT CORRELATE | | | WHEN COMPARING THE LIFE SAFETY PLAN (SHEET 1.6A) WITH | | | THE LIGHTING PLAN (SHEET 2.0E). | | | | | | *NEW COMMENT: | | | | | | A. PROVIDE SPECIFICATION FOR THE TENT/CANOPY FABRIC | | | FLAME RESISTANCE. | | | | | | B. PLEASE SHOW SPRINKLER HEAD LAYOUT TO ASSURE FIRE | | | PROTECTION UNDERNEATH THE CANOPIES. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE THE COMMENT WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561805-6722 |
|