| 2009-05-08 15:29:07 | **DENIED PLANS** |
| | |
| | |
| | |
| | 1) NOTE: COMPLIANCE WITH FBC 13-415.AB.5 CAN NOT BE |
| | DETERMINED. |
| | SOME LIGHTING ON PLANS IS STILL NOT COMPLETE. |
| | FOR EXAMPLE: PLEASE SEE ELEVATED DINING AREA WHICH |
| | LIGHTING PLANS SHOW SOME OF THE *D* FIXTURES TO LCP YET |
| | ON THE POWER PLANS THERE ARE *D* FIXTURES ARE NOT IN |
| | THE SAME LOCATION AND ARE NOT SHOWN CIRCUITED OR |
| | CONTROLLED BY LCP OR OTHER TYPE OF DEVICES. |
| | FOR EXAMPLE: PLEASE SEE G-1 FIXTURES WHICH BASED ON THE |
| | FIXTURE SYMBOLS AND NOTES ARE NOT DETERMINED AS ANY |
| | TYPE OF FIXTURE. |
| | FOR EXAMPLE: KITCHEN AREA LIGHTS CONTAIN NOTES ON PLANS |
| | WHICH MENTIONS TO CIRCUIT TO LCP HOWEVER THE PLANS DO |
| | NOT INDICATE ANY NEW OVER RIDES PER 13-415.AC.1.1, |
| | .1.2. |
| | |
| | 2) NOTE: PLEASE SEE 700.12F FOR CIRCUITING IF EMERGENCY |
| | AND EXIT LIGHTS. THERE ARE NUMEROUS NEW FIXTURES WHICH |
| | DO NOT SHOW ANY TYPE OF CIRCUITING. THERE ARE SOME |
| | FIXTURES WHICH ARE NOT CIRCUITED TO THE LOCAL LIGHTING |
| | IN ANY ONE AREA. SEE SAME FOR EXIT SIGNS. |
| | SEE FIRE MARSHAL REVIEW COMMENTS FOR REQUIRED EXIT |
| | SIGNS. (UPPER BAR AREA) SEE NFPA-101 7.8, 7.9 SOME ARE |
| | MISSING. |
| | |
| | 3) NOTE: PLEASE SEE ELECTRICAL RISER. THE RISER NEEDS |
| | TO BE COORDINATE WITH WHAT IS SHOWN ON RISER WITH |
| | PANELS. THERE ARE ALSO NEW CIRCUITS BEING ADDED TO |
| | PANELS SUCH AS PA WHICH THE PANEL SCHEDULE HAS NOT BEEN |
| | SUBMITTED. IN THE CONVERSATION WITH ELECTRICAL DESIGNER |
| | THE COMMENT WAS ONLY MADE TO THE EXISTING PANELS IN |
| | WHICH NO WORK WAS BEING DONE COULD BE DONE AS A |
| | PROVISO. HOWEVER THE PANELS IN WHICH THE PREDOMINANT |
| | AMOUNT OF WORK IS BEING DONE NEED TO COORDINATE WITH |
| | PLANS AND RISER. |
| | FOR EXAMPLE: PLEASE SEE RISER, ALL PANELS WITH THE |
| | EXCEPTION OF KA SECTION TWO ARE BEING FED FROM KA |
| | SECTION #1. HOWEVER BASED ON THE PANEL SCHEDULES FOR KA |
| | SECTION #1, THERE ARE NO PANELS LISTED. |
| | PLEASE COORDINATE. |
| | |
| | 4) NOTE: PLEASE SEE MULTIPLE RECEPTACLES WITH NO |
| | CIRCUITING. SOME HAVE NOTES CLOSE TO THE DEVICE AND |
| | SOME ARE MISSING CIRCUITS. |
| | 408.4, 240.4, 310.16, 220.14, 220.44 |
| | |
| | 5) NOTE: PANEL IN DEDICATE ELECTRICAL CLOSET STILL |
| | SHOWN ENCROACHING ON THE CLEAR SPACE REQUIRED PER |
| | 110.26 |
| | |
| | 6) NOTE: PLEASE PROVIDE WHERE THE TRANSFORMER IS |
| | LOCATED IN THE ROOM SHOWN ON PLANS. IS THIS ON FLOOR? |
| | PLEASE SEE 450.13, 110.26, 450.9, 450.21B ETC. |
| | |
| | |
| | ** ANY AND ALL LOW VOLTAGE SHALL BE UNDER SEPARATE |
| | PERMITS, FEES AND PLANS. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |