| Date |
Text |
| 2009-04-17 18:42:41 | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE: PLANS NEED TO BE UNDER THE 2006 NFPA101. ALL |
| | PLANS SUBMITTED AFTER DECEMBER 31ST 2008 |
| | FAC 69A-60.003, .004 |
| | PLANS REVIEWED UNDER NFPA-101 2006, NFPA-70 2005 AND |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 2) NOTE: PLEASE COMPLETE PLANS FOR ALL LIGHTING AND |
| | LIGHTING PERFORMANCE CALCULATIONS PER FBC 13-415.AB.5. |
| | PLANS MAKE REFERENCE TO 13-415.2.C.1, HOWEVER THAT CODE |
| | NO LONGER EXISTS IN THE CODE. |
| | PLEASE PROVIDE INFORMATION ON ALL LIGHTING FIXTURES |
| | SPECIFIC TO MANUFACTURE AND RATING OF FIXTURES. |
| | ALL FIXTURES SHALL BE INCLUDED IN THE CALCULATIONS |
| | UNLESS MEETING EXCEPTIONS. IF LIGHTING MEETS |
| | EXCEPTIONS, PLEASE IDENTIFY AND PROVIDE WHAT WILL MAKE |
| | THEM EXISTING. |
| | AS THERE IS MISSING INFORMATION A COMPLETE REVIEW CAN |
| | NOT BE DONE AT THIS TIME. |
| | |
| | ** PLEASE BE SURE ALL LIGHTING AS NOTED AND SHOWN |
| | CONTAINS A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. ( NRTL). 110.3 |
| | |
| | 3) NOTE: PLEASE SHOW COMPLIANCE WITH FBC 11-4.28.1,.2 |
| | AND .3 FOR ADA COMPLIANCE. |
| | |
| | 4) NOTE: PLEASE SUBMIT COMPLETE LOADS ON ALL PANELS. |
| | BELOW PANELS THERE ARE NOTES WHICH STATE ONLY NEW |
| | CIRCUITS ARE SHOWN. HOWEVER WITH THIS SAME STATEMENT |
| | THIS MEANS ONLY NEW LOADS ARE SHOWN AS NO OTHER LOADS |
| | ARE SHOWN. |
| | 220.12,220.14,220.42, 220.43, 220.44 ETC |
| | PLEASE SEE 215.3, 230.42 FOR CONTINUOUS LOADS. |
| | ** PLEASE KEEP IN MIND THE SHOW WINDOW LOADS. |
| | |
| | 5) NOTE: PLEASE COORDINATE ALL PANELS AND RISER |
| | DIAGRAM. PLEASE BE SURE TO COORDINATE WITH NOTES ABOVE |
| | FOR LOAD CALCULATIONS ALSO. |
| | THIS NOTE WILL BE BROKEN DOWN INTO MULTIPLE SECTIONS AS |
| | THERE ARE SEVERAL COORDINATION ITEMS WHICH NEED TO BE |
| | ADDRESSED. |
| | |
| | A) PLEASE SEE RISER AS PANEL *L* IS SHOW BEING FED FROM |
| | PANEL *KA SECTION 1* HOWEVER PER THE PANEL SCHEDULE |
| | SUBMITTED FOR THIS PANEL, NO PANEL *L* IS FED FROM THIS |
| | PANEL. PANEL *KA SECTION 2* ALSO DOES NOT LIST PANEL |
| | *L*. |
| | |
| | B) PLEASE SEE RISER AS PANEL *R* IS SHOWN BEING FED |
| | FROM *KA SECTION 1* HOWEVER BASED ON PANEL SCHEDULES OF |
| | BOTH SECTION ONE AND TWO, THE PANEL *R* IS ACTUALLY |
| | BEING FED FROM *KA SECTION 2*. |
| | |
| | C) PLEASE SEE RISER AS PANEL *KA SECTION * IS SHOWN |
| | BEING FED FROM *KA SECTION 2*. THIS SEEMS TO BE |
| | BACKWARDS AS THE SECTION 2 IS IN FRONT OF SECTION ONE. |
| | IN EITHER CASE NO MCB IS SHOWN IN SECTION ONE PANEL AND |
| | SECTION TWO PANEL WHICH IS SHOWN ON THE RISER AS ALL |
| | TAPPED CONDUCTORS SHALL TERMINATE IN OVER CURRENT |
| | PROTECTION. IN EITHER CASE A MAIN NEEDS TO BE |
| | INSTALLED. 240.21 |
| | ALSO, WHICH PANEL IS ACTUALLY THE FIRST PANEL SECTION? |
| | |
| | D) PLEASE SEE RISER AS THERE ARE TWO LIGHTING CONTROL |
| | PANELS BEING SHOWN WHEN THERE IS ONLY ONE SCHEDULE |
| | SUBMITTED FOR ONE LIGHTING CONTROL PANEL. |
| | |
| | E) PLEASE COORDINATE ALL PANELS AND LOCATIONS OF ALL |
| | SERVICE EQUIPMENT. PLEASE SEE EQUIPMENT PLANS AS THE |
| | UNIVERSAL SYMBOL FOR AN ELECTRICAL PANEL INDICATES TWO |
| | PANELS WHICH ARE NOT ON ANY OTHER SHEETS. THESE ARE IN |
| | THE KITCHEN AREA NEAR EQUIPMENT NUMBERS 34,35. |
| | ARE THESE PANELS? |
| | WHERE IS PANEL PA? |
| | PLEASE SEE THE TWO LCP ON PLANS DO NOT MEET 110.26 AS |
| | BOTH ARE SHOWN WITH OVER LAP WHICH ONE WOULD AFFECT THE |
| | OTHER FOR CODE SECTION GIVEN. THESE MAY ALSO NOT BE |
| | LOCATED IN ANY TYPE OF STORAGE CLOSET. |
| | 110.26, 240.24 |
| | |
| | |
| | PLEASE GO OVER ALL PANELS, CIRCUITS, TAPPED CONDUCTORS, |
| | ETC. SOME ITEMS ARE NOTED FOR BENEFIT HOWEVER ARE NOT |
| | ALL ITEMS. |
| | 240.21,215.5, 240.4, 310.16, 408.4, 408.36 ETC |
| | |
| | 6) NOTE: ** NOTED FOR INFORMATIONAL PURPOSE. THE LOW |
| | VOLTAGE SYSTEMS AS SHOWN ON PLANS SUCH AS SPEAKERS, |
| | PHONE CATV SHALL BE REQUIRED TO BE UNDER SEPARATE |
| | PERMIT(S) |
| | THESE PLANS MAY BE REFERENCED FOR TURN AROUND PERMITS |
| | HOWEVER SEPARATE FEES AND PERMIT APPLICATION(S) ARE |
| | REQUIRED. |
| | |
| | 7) NOTE: PLEASE BE SURE TO COMPLY WITH FBC |
| | 13-415.1.AB.1.1, .1.2 AND .1.3 FOR LIGHTING CONTROLS. |
| | ** SEE SEPARATE CONTROLS** |
| | PLEASE ALSO SEE AREAS SUCH AS CORRIDOR WHICH DOES NOT |
| | INDICATE ANY OVER RIDE OR CONTROLS. |
| | ** IF USING ANY EXCEPTIONS FOR LIGHTS WHICH CAN NOT |
| | SEEN BY THE OCCUPANT, THEN PLEASE PROVIDE SPECIFIC |
| | DETAIL FOR ANY PROPOSED KEYPADS WHICH MUST |
| | CONTAIN*PILOT/INDICATOR LIGHTS*. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |