Plan Review Notes
Plan Review Notes For Permit 09040319
Permit Number 09040319
Review Stop B
Sequence Number 3
Notes
Date Text
2009-05-18 09:29:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE SPAN FOR ALL OPENINGS IS THE SAME AS OPENING
 SIZE. HOW IS THIS POSSIBLE WITH A 3" EDGE DISTANCE AND
 C2 (WALL MOUNT) CONNECTION? AT A MINIMUM, SPAN SHOULD
 BE AT LEAST 3" LARGER THAN THE OPENING. THIS COMMENT
 AFFECTS ANCHORING FOR OPENING 2; WHEN 3" IS ADDED TO
 103", THE COLUMN FOR "SPANS UP TO 8'8"" CAN NO LONGER
 BE USED (8'8" = 104"). PLEASE CLARIFY SPANS.
  
 2. OPENINGS OVER 104" MUST USE THE COLUMN FOR "SPANS UP
 TO 13'", SEE PAGE 11 OF PRODUCT APPROVAL. OPENING 2 IS
 IN QUESTION (MUST FIRST DETERMINE CORRECT SPAN).
 OPENING 1 REQUIRES 5" ON BOTTOM, NOT 8".
  
 PLEASE CHECK ALL OPENINGS.
  