Plan Review Notes
Plan Review Notes For Permit 09040303
Permit Number 09040303
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-13 15:54:53MAINS TO BE GROUPED 230.72
  
 NO MORE THAN 8FT OF SEC INSIDE.
  
 PARALLEL CONDUCTORS ARE NOT PERMITTED SMALLER THAN 1/0.
  
 ABOVE REDLINED ON RISER/PLANS.