| Plan Review Notes For Permit 09040303 |
| Permit Number |
09040303 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-13 15:54:53 | MAINS TO BE GROUPED 230.72 | | | | | | NO MORE THAN 8FT OF SEC INSIDE. | | | | | | PARALLEL CONDUCTORS ARE NOT PERMITTED SMALLER THAN 1/0. | | | | | | ABOVE REDLINED ON RISER/PLANS. |
|