| 2009-04-30 09:33:33 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | FBC-2007 PLUMBING |
| | CITY WPB AMENDMENTS (CHAPTER 1) |
| | |
| | 1. SHT P.1 SECOND FLOOR PLUMBING PLAN & SANITARY RISER |
| | DIAGRAM. PER TABLE 906.1 THE MAXIMUM DISTANCE OF |
| | FIXTURE TRAP FROM THE VENT IS 8 FEET FOR 2". THE SHOWER |
| | SCALES OUT TO APPROX. 13 FEET. PLEASE SHOW CORRECT |
| | VENTING FOR THE SHOWER. |
| | |
| | 2. SHT P.1 DETAIL 2 SECOND FLOOR SANITARY AND SECOND |
| | FLOOR PLUMBING PLAN SHOW A 2ND LAV ON THE SANITARY |
| | PIPING BUT THE 2ND LAV IS NOT SHOWN ON THE FLOOR PLAN |
| | NOR ON THE FLOOR PLAN ON SHT A.1 DETAIL 2. PLEASE |
| | CORRELATE. SECTIONS 106.1.1 & 405.3.1. |
| | |
| | 3. SHT P.1 INDICATES A TANKLESS GAS WATER HEATER. |
| | SEPARATE GAS PERMIT & PLANS SHALL BE SUBMITTED. SECTION |
| | 105.1. |
| | |
| | 4. SHT S.4 SIZING OF THE VERTICAL LEADERS & OVERFLOW |
| | SCUPPERS IS INDICATED AS BEING FROM THE FBC-2004 |
| | EDITION. THE PRESENT CODE CYCLE IS THE FBC-2007 |
| | EDITION. PLEASE SHOW DESIGN FROM THE CORRECT CODE |
| | CYCLE. SECTION. ALSO THE CALCULATIONS INDICATE LEADERS |
| | PROVIDED. THE PLANS DO NOT SHOW LEADERS. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |