2009-04-30 09:33:33DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 CITY WPB AMENDMENTS (CHAPTER 1)
  
 1. SHT P.1 SECOND FLOOR PLUMBING PLAN & SANITARY RISER
 DIAGRAM. PER TABLE 906.1 THE MAXIMUM DISTANCE OF
 FIXTURE TRAP FROM THE VENT IS 8 FEET FOR 2". THE SHOWER
 SCALES OUT TO APPROX. 13 FEET. PLEASE SHOW CORRECT
 VENTING FOR THE SHOWER.
  
 2. SHT P.1 DETAIL 2 SECOND FLOOR SANITARY AND SECOND
 FLOOR PLUMBING PLAN SHOW A 2ND LAV ON THE SANITARY
 PIPING BUT THE 2ND LAV IS NOT SHOWN ON THE FLOOR PLAN
 NOR ON THE FLOOR PLAN ON SHT A.1 DETAIL 2. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 405.3.1.
  
 3. SHT P.1 INDICATES A TANKLESS GAS WATER HEATER.
 SEPARATE GAS PERMIT & PLANS SHALL BE SUBMITTED. SECTION
 105.1.
  
 4. SHT S.4 SIZING OF THE VERTICAL LEADERS & OVERFLOW
 SCUPPERS IS INDICATED AS BEING FROM THE FBC-2004
 EDITION. THE PRESENT CODE CYCLE IS THE FBC-2007
 EDITION. PLEASE SHOW DESIGN FROM THE CORRECT CODE
 CYCLE. SECTION. ALSO THE CALCULATIONS INDICATE LEADERS
 PROVIDED. THE PLANS DO NOT SHOW LEADERS. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  