Plan Review Notes
Plan Review Notes For Permit 09040297
Permit Number 09040297
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-21 12:08:12 
  
  
 APPLICATION #09040297 ELECTRICAL PLAN REVIEW
 333 PILGRIM ROAD 4/21/09
 WEST PALM BEACH, FL.
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET E1UNLESS OTHERWISE NOTED.
  
 1} SHEET A.0 REFERENCES REAR APARTMENT SHEETS BUT NONE
 WERE SUBMITTED, THE APPLICATION ONLY MENTIONS WORK TO
 THE MAIN HOUSE BUT HAS BEEN ALTERED WITH WHITE OUT.
 INDICATE THE INTENTION OF THE SCOPE OF WORK AND SUBMIT
 PLANS ACCORDINGLY. 106.1.1 FBC AS AMENDED.
  
 2} LOCATE THE DISCONNECT FOR THE MAIN HOUSE ON THE
 PLAN. 225.31.
  
 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE PARTITION WALLS BETWEEN THE
 LIVING ROOM AND DINING ROOM.
  
 4} THE HALLWAY ON THE SECOND FLOOR PLAN (SHEET E.2) IS
 REQUIRED TO HAVE A RECEPTACLE PER 210.52(H).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  