| Plan Review Notes For Permit 09040297 |
| Permit Number |
09040297 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-21 12:08:12 | | | | | | | | | | APPLICATION #09040297 ELECTRICAL PLAN REVIEW | | | 333 PILGRIM ROAD 4/21/09 | | | WEST PALM BEACH, FL. | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | ALL COMMENTS RELATE TO SHEET E1UNLESS OTHERWISE NOTED. | | | | | | 1} SHEET A.0 REFERENCES REAR APARTMENT SHEETS BUT NONE | | | WERE SUBMITTED, THE APPLICATION ONLY MENTIONS WORK TO | | | THE MAIN HOUSE BUT HAS BEEN ALTERED WITH WHITE OUT. | | | INDICATE THE INTENTION OF THE SCOPE OF WORK AND SUBMIT | | | PLANS ACCORDINGLY. 106.1.1 FBC AS AMENDED. | | | | | | 2} LOCATE THE DISCONNECT FOR THE MAIN HOUSE ON THE | | | PLAN. 225.31. | | | | | | 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND | | | 210.52(A)(2). 2005 NEC. SEE PARTITION WALLS BETWEEN THE | | | LIVING ROOM AND DINING ROOM. | | | | | | 4} THE HALLWAY ON THE SECOND FLOOR PLAN (SHEET E.2) IS | | | REQUIRED TO HAVE A RECEPTACLE PER 210.52(H). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|