2009-04-20 10:04:33BUILDING PLAN REVIEW
 PERMIT: 09040297
 ADD: 333 PILGRIM RD
 CONT: O/B RANDALL & KIMBERLY WOLF
 TEL: (561)628-2458
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO
 THE 2007 FBC RESIDENETIAL BUILDING CODE WITH THE 2009
 SUPPLEMENTS AND THE 2007 EXISTING FLORIDA BUILDING CODE
 WITH 2009 SUPPLEMENTS CHAPTER:
 CHAPTER 4; 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 403, 404 AND 405 OF THIS CODE.
 CHAPTER 10 ADDITIONS
 CHAPTER 11 HISTORIC BUILDING : A CONTRIBUTING BUILDING
  
 2) THERE APPEARS TO BE A DISCREPANCY BETWEEN THE PLANS
 AND THE PERMIT APPLICATION. THE PERMIT APPLICATION
 INDICATES UNDER THE DESCREPTION OF WORK, "MAIN HOUSE
 AND ADDITION". THE PERMIT SEET OF PLANS ALSO INCLUDES
 WORK TO BE COMPLETED ON THE REAR APPARTMENT;
 1) REPLACEMENT OF WINDOWSON THE REAR APARTMENT.
 2) NEW EXTERIOR STAIRS AT THE EXTERIOR APARTMENT.
 3) NEW OVERHANG AT REAR APARTMENT ( SEE ELEVATIONS)
 ELEVATION SHEETS A.2 & A.3 ARE OF THE MAIN HOUSE ONLY!
  
 THE INDEX ALSO FOUND ON THE COVERSHEET OF THE PLANS
 INDICATES THERE TO BE SHEETS CH.1, CH.2, CH-S.2 &
 CH-S.3 WHICH WERE NOT FOUND WITHIN THE PERMIT SET OF
 DOCUMENTS. IF THIS WORK IS TO BE PART OF THIS PROJECT
 IT WOULD BE MORE EFFICIENT TWO CREATE A SECOND PERMIT
 FOR THE REAR APARTMENT. THE INSPECTIONS WOULD BE ABLE
 TO BE IDENTIFIED AS TO WHICH BUILDING EACH INSPECTION
 WOULD HAVE BEEN TIED TO FOR RECORD RETENTION PURPOSES.
  
  
 3) 1105.1 STRICT COMPLIANCE. HISTORIC STRUCTURES OR
 PORTIONS OF SUCH STRUCTURES THAT DO NOT STRICTLY COMPLY
 WITH THIS CODE SHALL BE CONSIDERED TO BE IN COMPLIANCE
 IF IT CAN BE SHOWN TO THE SATISFACTION OF THE BUILDING
 CODE OFFICIAL THAT EQUIVALENT PROTECTION HAS BEEN
 PROVIDED OR THAT NO HAZARD WILL BE CREATED OR CONTINUED
 THROUGH NONCOMPLIANCE.
  
 1105.2 COMPLIANCE OPTION. LIFE SAFETY AND PROPERTY
 CONSERVATION SHALL BE PROVIDED IN ACCORDANCE WITH ONE
 OF THE FOLLOWING OPTIONS:
  
 1. PRESCRIPTIVE-BASED PROVISIONS OF THIS CODE.
  
 2. COMPLIANCE ALTERNATIVE-BASED PROVISIONS OF THIS
 CODE.
  
 3. PERFORMANCE-BASED PROVISIONS OF NFPA 914, CODE FOR
 FIRE PROTECTION OF HISTORIC STRUCTURES, CHAPTER 6,
 ALONG WITH A STRUCTURAL EVALUATION AS SPECIFIED IN
 SECTION 1201.4.1 OF THIS CODE.
  
 4) 1106.1 INVESTIGATION AND EVALUATION REPORT. AN
 HISTORIC BUILDING UNDERGOING ALTERATION OR CHANGE OF
 OCCUPANCY SHALL BE INVESTIGATED AND EVALUATED. IF IT IS
 INTENDED THAT THE BUILDING MEET THE REQUIREMENTS OF
 THIS CHAPTER, A WRITTEN REPORT SHALL BE PREPARED AND
 FILED WITH THE BUILDING OFFICIAL BY A
 FLORIDA-REGISTERED ARCHITECT OR ENGINEER. SUCH REPORT
 SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF SECTIONS
 4.3.1.2 THROUGH 4.3.2 OF NFPA 914, CODE FOR FIRE
 PROTECTION OF HISTORIC STRUCTURES AND SHALL IDENTIFY
 EACH REQUIRED SAFETY FEATURE THAT IS IN COMPLIANCE WITH
 THIS CHAPTER AND WHERE COMPLIANCE WITH THIS OR OTHER
 CHAPTERS WOULD BE DAMAGING TO THE CONTRIBUTING HISTORIC
 FEATURES. IN ADDITION, THE REPORT SHALL DESCRIBE EACH
 FEATURE THAT IS NOT IN COMPLIANCE AND DEMONSTRATE HOW
 THE INTENT OF THE PROVISIONS OF THIS OR OTHER CHAPTERS
 ARE COMPLIED WITH IN PROVIDING AN EQUIVALENT LEVEL OF
 SAFETY.
  
 5A) PLANS DO NOT INDICATE A VENTED UNDER FLOOR
 SPACE.R408.3 UNVENTED CRAWL SPACE.
 VENTILATION OPENINGS IN UNDER-FLOOR SPACES SPECIFIED IN
 SECTIONS R408.1 AND R408.2 SHALL NOT BE REQUIRED WHERE:
  
 1. EXPOSED EARTH IS COVERED WITH A CONTINUOUS VAPOR
 RETARDER. JOINTS OF THE VAPOR RETARDER SHALL OVERLAP BY
 6 INCHES (152 MM) AND SHALL BE SEALED OR TAPED. THE
 EDGES OF THE VAPOR RETARDER SHALL EXTEND AT LEAST 6
 INCHES (152 MM) UP THE STEM WALL AND SHALL BE ATTACHED
 AND SEALED TO THE STEM WALL; AND
  
 2. ONE OF THE FOLLOWING IS PROVIDED FOR THE UNDER-FLOOR
 SPACE:
  
 2.1. CONTINUOUSLY OPERATED MECHANICAL EXHAUST
 VENTILATION AT A RATE EQUAL TO 1 CFM (0.47 L/S) FOR
 EACH 50 FT2 (4.7 M2) OF CRAWLSPACE FLOOR AREA,
 INCLUDING AN AIR PATHWAY TO THE COMMON AREA (SUCH AS A
 DUCT OR TRANSFER GRILLE), AND PERIMETER WALLS INSULATED
 IN ACCORDANCE WITH SECTION N1102.B;
  
 2.2. CONDITIONED AIR SUPPLY SIZED TO DELIVER AT A RATE
 EQUAL TO 1 CFM (0.47 L/S) FOR EACH 50 FT2 (4.7 M2) OF
 UNDER-FLOOR AREA, INCLUDING A RETURN AIR PATHWAY TO THE
 COMMON AREA (SUCH AS A DUCT OR TRANSFER GRILLE), AND
 PERIMETER WALLS INSULATED IN ACCORDANCE WITH SECTION
 N1102.B;
  
 2.3. PLENUM COMPLYING WITH SECTION N110.ABC.3.6, IF
 UNDER-FLOOR SPACE IS USED AS A PLENUM.
  
 5B) PLANS FAIL TO INDICATE UNDER THE FLOOR ACCESS AS
 PER R408.4.
  
 6) SHEET A1 DOES NOT INDICATE ATTIC ACCESS:R807.1 ATTIC
 ACCESS. BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO
 ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M2) AND
 HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR MORE.
  
 7) SHEET A3 INDICATES ROOFING UNDERLAYMENT NOTES FOR
 NEW SPANISH STYLE ROOFING, THE UNDERLAYMENT NOTES READ
 FOR THAT OF SHINGLES FOR ROOFS WITH LESS THAN A 4/12
 PITCH, PLEASE CORRECT THE UNDERLAYMENT NOTES AS PER
 R905.4.3 UNDERLAYMENT. UNDERLAYMENT SHALL COMPLY WITH
 ASTM D 226, TYPE I OR TYPE II OR ASTM D 1970 OR ASTM D
 4869. UNDERLAYMENT SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. SEE
 THE MIAMI- DADE NOA FOR REQUIREMENTS.
  
 THE MIAMI-DADE NOA FOR ARTEZANOS WORLD CLASS TWO PIECE
 HANDMADE TAPERED MISSION BARREL ROOF TILE UNDER TABLE 4
 HAS TWO TYPES OF APPLICATION, A MORTAR SET AND ADHESIVE
 SET SYSTEM.
 PLEASE CIRCLE WHICH SYSTEM IS TO BE INSTALLED WITH THE
 APPROPRIATE FOOT POUNDS.
  
 8) SHEET A-4 DETAIL 5 /S3 INDICATES A SINGLE PLY
 MEMBRANE ROOF THE OWNER SUBMITTED A MIAMI-DADE NOA
 TARCO 30# ASTM SPECIFICATION FELT EASY LAY, FAST 90,
 PS200 REPORT NOA 07-0717.04 THIS REPORT INDICATES IT IS
 TO BE USED WITH ROOF TILE, NO PRODUCT APPROVALS HAVE
 BEEN SUBMITTED FOR THE BALCONY COVERED FLOOR (FLOOR)
 THAT CAN BE USED AS A WALKABLE DECK AREA.
  
 9) SHEET S.1 THE PLANS INDICATE IN MULTIPLE AREAS THAT
 THE WIND DESIGN WAS DESIGNED UNDER ASCE 7-02, THE
 CURRENT 2007 FBC RESIDENTIAL IS DESIGNED UNDER THE ASCE
 7-05 SEE REFRENCED STANDARDS.
  
 10) SHEET S-1 SECTION D-4 ROOF LOADING INDICATES DEAD
 LOADBOTTOM CORD OF 10 LBS WHEREAS SHEET S-4 INDICATES A
 DEAD LOAD OF 10 LBS AND LIVE LOAD OF 10LBS. TABLE
 R301.5 ATTICS WITHOUT STORAGE
 INDICATE 10 LBS. LIVE LOAD.
  
 11) THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS. PLEASE PROVIDE WHERE COMPLIANCE IS
 TO BE MET.
  
 12) GUARD RAIL SHEET S-3 DETAIL# 5 INDICATES THE USE OF
 A WOOD GUARD RAIL SYSTEM PLEAE PROVIDE CALCULATIONS HOW
 200 LBS LIVE LOAD WILL BE MET TABLE R301.5 FOOTNOTE D.
 A SINGLE CONCENTRATED LOAD APPLIED IN ANY DIRECTION AT
 ANY POINT ALONG THE TOP.
  
 13) DISCREPANCY BETWEEN S.2 DETAIL# 3 AND SHEET S-4
 STRUCTURAL CONNECTIONS. SHEET S-2 INDICATES THE USE OF
 1/4" TAPCONS AT 32" O.C. WHERE AS S.4 INDICATES THE USE
 OF 1?2 INCHX 5 INCH WEDGE ANCHORS AT 32" O. C.
  
 14) RADON FEES OWED OF $21.04.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved