Plan Review Notes
Plan Review Notes For Permit 09040295
Permit Number 09040295
Review Stop E
Sequence Number 2
Notes
Date Text
2010-02-10 08:50:05*REDLINED/PROVISO*
  
 PLEASE REVISE PLANS BEFORE FINAL. IF THERE ARE OTHER
 REVISIONS OR SUBSTANTIAL CHANGES THEN THOSE CHANGES
 WILL NEED TO BE REVISED BEFORE ROUGH.
  
  
 1) NOTE: SMOKE DETECTOR ADDED TO LAUNDRY ROOM. HOWEVER
 THAT WAS NOT THE PREVIOUS COMMENT. PLEASE SEE FBC
 R313.1 AND 313.4 WHICH REQUIRES SMOKE ALARMS AND CARBON
 MONOXIDE ALARM(S) TO MEET CURRENTS CODES WHEN DOING
 WORK AS DESCRIBE IN THE SECTIONS NOTED.
 PLEASE SEE NFPA-72 11.5.1, 118.3 FOR SMOKE ALARM
 LOCATIONS.
 PLEASE REVISE TO SHOW LOCATIONS AS REQUIRED INSIDE AND
 OUTSIDE SLEEPING ROOMS. PLANS SHOW ONE IN LAUNDRY ROOM
 HOWEVER IT IS NOT REQUIRED IN THE LAUNDRY ROOM.
  
 2) NOTE: LOAD CALCULATIONS DO NOT COORDINATE WITH THE
 SUBMITTED PANEL SCHEDULE. FOR EXAMPLE, THE ADDITIONAL
 ONE OR MORE SMALL APPLIANCE CIRCUIT(S) SHALL BE FIGURED
 AT 1500VA. THIS WOULD REQUIRE 1500VA FOR THE TWO
 MINIMUM AND 1500VA FOR EACH ABOVE THE TWO.
 210.11C1, 220.52
 LOAD CALCULATIONS STATE THERE ARE 57 CIRCUITS, HOWEVER
 PANEL SCHEDULE SHOWS PANEL BEING A 20 CIRCUIT PANEL?
 408.4.
  
 3) NOTE: NO MINIMUM CONDUCTOR SIZES PER NEC 310.16 ON
 PANEL SCHEDULE.
  
 4) NOTE: BASED ON THE SYMBOL LEGEND, THE WASHER
 RECEPTACLE IS SHOWN AS A DUPLEX WHEN IT IS REQUIRED TO
 BE A DEDICATED SINGLE RECEPT.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  