| 2010-02-10 08:50:05 | *REDLINED/PROVISO* |
| | |
| | PLEASE REVISE PLANS BEFORE FINAL. IF THERE ARE OTHER |
| | REVISIONS OR SUBSTANTIAL CHANGES THEN THOSE CHANGES |
| | WILL NEED TO BE REVISED BEFORE ROUGH. |
| | |
| | |
| | 1) NOTE: SMOKE DETECTOR ADDED TO LAUNDRY ROOM. HOWEVER |
| | THAT WAS NOT THE PREVIOUS COMMENT. PLEASE SEE FBC |
| | R313.1 AND 313.4 WHICH REQUIRES SMOKE ALARMS AND CARBON |
| | MONOXIDE ALARM(S) TO MEET CURRENTS CODES WHEN DOING |
| | WORK AS DESCRIBE IN THE SECTIONS NOTED. |
| | PLEASE SEE NFPA-72 11.5.1, 118.3 FOR SMOKE ALARM |
| | LOCATIONS. |
| | PLEASE REVISE TO SHOW LOCATIONS AS REQUIRED INSIDE AND |
| | OUTSIDE SLEEPING ROOMS. PLANS SHOW ONE IN LAUNDRY ROOM |
| | HOWEVER IT IS NOT REQUIRED IN THE LAUNDRY ROOM. |
| | |
| | 2) NOTE: LOAD CALCULATIONS DO NOT COORDINATE WITH THE |
| | SUBMITTED PANEL SCHEDULE. FOR EXAMPLE, THE ADDITIONAL |
| | ONE OR MORE SMALL APPLIANCE CIRCUIT(S) SHALL BE FIGURED |
| | AT 1500VA. THIS WOULD REQUIRE 1500VA FOR THE TWO |
| | MINIMUM AND 1500VA FOR EACH ABOVE THE TWO. |
| | 210.11C1, 220.52 |
| | LOAD CALCULATIONS STATE THERE ARE 57 CIRCUITS, HOWEVER |
| | PANEL SCHEDULE SHOWS PANEL BEING A 20 CIRCUIT PANEL? |
| | 408.4. |
| | |
| | 3) NOTE: NO MINIMUM CONDUCTOR SIZES PER NEC 310.16 ON |
| | PANEL SCHEDULE. |
| | |
| | 4) NOTE: BASED ON THE SYMBOL LEGEND, THE WASHER |
| | RECEPTACLE IS SHOWN AS A DUPLEX WHEN IT IS REQUIRED TO |
| | BE A DEDICATED SINGLE RECEPT. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |