Plan Review Notes
Plan Review Notes For Permit 09040295
Permit Number 09040295
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-27 14:34:39**DENIED PLANS**
  
  
 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION AFTER
 MARCH 1ST, 2009 SHALL BE UNDER THE DESIGN OF THE 2007
 FBC WITH 2009 AMENDMENTS.
  
 2007 FBC W/ 2009 REVISIONS.
 2005 NFPA-70
  
 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS/ DETAILS FOR
 THE ELECTRICAL SCOPE OF WORK. THE FLOOR PLAN HAS SOME
 ITEMS HOWEVER NOT COMPLETE FOR CODE COMPLIANT FOR A NEW
 LAUNDRY ROOM.
 PLEASE SHOW LOCATIONS OF NEW LAUNDRY EQUIPMENT.
 PLEASE BE SURE TO SEE THAT LAUNDRY AND WASHER CIRCUITS
 SHALL BE DEDICATED AND REQUIRED SIZING PER 210.52F,
 210.11C2, AND LOADS PER 220.52.
 PLEASE SEE 220.54 FOR ELECTRIC DRYERS.
 PLEASE SEE 310.16, 240. FOR SIZING OF CONDUCTORS.
 PLEASE SEE 210.8A7 FOR REQUIRED GFCI PROTECTION.
 PLEASE SEE 210.70 FOR LIGHTING FOR ROOM AND EGRESS
 EXIT.
 ETC
 ** PLEASE SEE 220 FOR LOAD CALCULATIONS
 ** PLEASE SHOW PANEL SCHEDULE FOR DEDICATED NEW
 CIRCUITS. BREAKER SIZES AS NOTED ABOVE FOR BRANCH
 CIRCUITS.
  
 3) NOTE: PLEASE SEE FBC R313 AND NFPA-72 11.5.1. PLEASE
 SHOW ALL EXISTING OR NEW SMOKE ALARMS AS REQUIRED.
  
 *** IMPORTANT: AS MOST ELECTRICAL IS NOT SHOWN FOR
 MINIMUM COMPLIANCE IT IS NOT POSSIBLE TO GIVE A FULL
 REVIEW FOR CODE COMPLIANCE. THERE MAY BE NEW COMMENTS
 ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  