| 2009-04-27 14:34:39 | **DENIED PLANS** |
| | |
| | |
| | 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION AFTER |
| | MARCH 1ST, 2009 SHALL BE UNDER THE DESIGN OF THE 2007 |
| | FBC WITH 2009 AMENDMENTS. |
| | |
| | 2007 FBC W/ 2009 REVISIONS. |
| | 2005 NFPA-70 |
| | |
| | 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS/ DETAILS FOR |
| | THE ELECTRICAL SCOPE OF WORK. THE FLOOR PLAN HAS SOME |
| | ITEMS HOWEVER NOT COMPLETE FOR CODE COMPLIANT FOR A NEW |
| | LAUNDRY ROOM. |
| | PLEASE SHOW LOCATIONS OF NEW LAUNDRY EQUIPMENT. |
| | PLEASE BE SURE TO SEE THAT LAUNDRY AND WASHER CIRCUITS |
| | SHALL BE DEDICATED AND REQUIRED SIZING PER 210.52F, |
| | 210.11C2, AND LOADS PER 220.52. |
| | PLEASE SEE 220.54 FOR ELECTRIC DRYERS. |
| | PLEASE SEE 310.16, 240. FOR SIZING OF CONDUCTORS. |
| | PLEASE SEE 210.8A7 FOR REQUIRED GFCI PROTECTION. |
| | PLEASE SEE 210.70 FOR LIGHTING FOR ROOM AND EGRESS |
| | EXIT. |
| | ETC |
| | ** PLEASE SEE 220 FOR LOAD CALCULATIONS |
| | ** PLEASE SHOW PANEL SCHEDULE FOR DEDICATED NEW |
| | CIRCUITS. BREAKER SIZES AS NOTED ABOVE FOR BRANCH |
| | CIRCUITS. |
| | |
| | 3) NOTE: PLEASE SEE FBC R313 AND NFPA-72 11.5.1. PLEASE |
| | SHOW ALL EXISTING OR NEW SMOKE ALARMS AS REQUIRED. |
| | |
| | *** IMPORTANT: AS MOST ELECTRICAL IS NOT SHOWN FOR |
| | MINIMUM COMPLIANCE IT IS NOT POSSIBLE TO GIVE A FULL |
| | REVIEW FOR CODE COMPLIANCE. THERE MAY BE NEW COMMENTS |
| | ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS |
| | TIME. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |