Plan Review Notes
Plan Review Notes For Permit 09040295
Permit Number 09040295
Review Stop B
Sequence Number 1
Notes
Date Text
2009-05-11 11:12:42RESIDENTIAL (R3) REMODELING, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE.
  
 1- PLANS NEED TO BE DESIGNED PER FBC 2007 NOT FBC 2001.
 REVISE GENERAL NOTE #1 IN ALL DRAWINGS SUBMITTED.
  
 2- NEED TO PROVIDE THE NAME AND SIGNATURE OF THE DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THIS
 STRUCTURE. IF THE DESIGN PROFESSIONAL IS AN ARCHITECT
 OR ENGINEER, THEN PLANS NEED TO BE SIGNED AND SEALED
 ACCORDINGLY AS REQUIRED BY CHAPTER 481/471 FLORIDA
 STATUTES. SEC. 106.1 CITY AMENDMENTS TO FBC.
  
 3- PROVIDE ALL DESIGN INFORMATION REQUIRED BY SEC.
 R301.1 OF 2007 FLORIDA RESIDENTIAL CODE. SPECIFY ALL
 DESIGN LOADS. SPECIFY ALL DEAD LOADS, LIVE LOADS, ROOF
 LOADS AND WIND LOADS.
 ALSO, SPECIFY ALL DESIGN PRESSURES FOR DOORS AND
 WINDOWS.
  
 4- PROVIDE SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 PROTECTION AGAINST WOOD DECAY FOR FLOOR JOISTS ON FIRST
 FLOOR CRAWLING AREA AS REQUIRED BY SEC. R319 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 5- ALL FLOOR FRAMING PLANS AND DETAILS SECTIONS NEED TO
 PROVIDE COMPLETE INFORMATION SHOWING ALL CONNECTORS
 THAT PROVIDE A CONTINUOUS LOAD PATH AS REQUIRED BY SEC.
 R601.2 OF 2007 FLORIDA RESIDENTIAL CODE. EG: FLOOR
 FRAMING PLANS ON SHEET A-2 ARE MISSING CONNECTIONS OF
 2X10 FLOOR JOISTS ON BOTH ENDS, INCLUDING ATTACHMENT OF
 LEDGERS. WALL SECTIONS ON SHEET A-5 DON'T PROVIDE
 COMPLETE INFORMATION FOR CONNECTION OF 2X10 JOIST TO
 BEARING WALLS.. WALL SECTIONS ARE MISSING ATTACHMENT OF
 2X4 STUDS AT BOTTOM END.
  
 6- PROVIDE 2 COPIES OF EACH PRODUCT APPROVALS AS
 REQUIRED BY DCA RULE 9B-72 FOR:
 A) EXTERIOR DOOR. CLARIFY WHICH PRODUCT APPROVAL IS
 GOING TO BE USED. THERE ARE TWO DIFFERENT PRODUCT
 APPROVALS SUBMITTED. CLARIFY IF USING NOA 07-0820.08
 (JELD-WEN DOOR) OR OTHER PRODUCT FROM MASONITE
 INTERNATIONAL.
 NOTE: MASONITE INTERNATIONAL PRODUCT APPROVAL SUBMITTED
 IS INCOMPLETE AND NEED STORM SHUTTERS. NEED TO PROVIDE
 COVER PAGE OF PRODUCT APPROVAL AND COMPLETE INFORMATION
 FOR STORM SHUTTERS INCLUDING SHUTTERS PRODUCT APPROVAL
 AND COMPLETE INSTALLATION SCHEDULE.
  
 B) SINGLE HUNG WINDOWS. PROVIDE 2 COPIES. ONLY ONE
 SUBMITTED.
  
 C) FLAT ROOF PRODUCT APPROVAL: * INDICATE WHICH
 APPROVED ASSEMBLY FROM NOA 05-0819.05 IS GOING TO BE
 USED. ** SPECIFY WHICH BASE SHEET FASTENING OPTION IS
 GOING TO BE USED. *** PROVIDE RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7. SEE LAST PAGE ON NOA
 SUBMITTED.
  
 7- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 8- OWES $62.17. PERMIT VALUATION WAS NOT ENTERED AT
 TIME OF PERMIT APPLICATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712