| 2009-06-01 17:05:52 | ** DENIED 2ND REVIEW** |
| | |
| | 1) NOTE: PLEASE SEE 13-415.AB.5 UNDER THE FBC 2007 WITH |
| | 2009 REVISIONS. |
| | THE ADDITIONAL ALLOWANCE PREVIOUSLY PERMITTED FOR |
| | ACCENT, SCONCE LIGHTING ETC IS NO LONGER UNDER THE NEW |
| | CODE. |
| | THE AREAS ARE SPECIFIC TO SPACES. BASED ON THE |
| | ALLOWANCES UNDER THE NEW CODE, THE AMOUNT SHOWN EXCEEDS |
| | TABLES. |
| | THE FIXTURE SCHEDULE NEEDS TO COORDINATE. SEE WALL HUNG |
| | FIXTURE AS THIS STATES IT IS INCANDESCENT AND SHOWS A |
| | 26W FLUORESCENT BULB. THIS IS NOT POSSIBLE. |
| | PLEASE BE SURE TO COME UP WITH SOME SORT OF FIXTURE |
| | MEETING MINIMUM CODE AT THIS TIME. FIXTURES MAY ALWAYS |
| | BE REVISED ALONG WITH THE TABLE CALCULATIONS AT A LATER |
| | DATE. |
| | |
| | |
| | ** AS GONE OVER WITH ENGINEER THE MOTION SENSORS WHICH |
| | ARE SPECIFICALLY STATED ON PLANS TO BE *MOTION ONLY* |
| | MAY ACTUALLY BE OCCUPANCY SENSORS WHICH ARE DUAL |
| | TECHNOLOGY. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |