| Date |
Text |
| 2009-04-30 14:40:53 | DENIED |
| | REFERENCE: |
| | FBC-2007 EXISTING BUILDING |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 11 |
| | |
| | 1. THE CODE CYCLE FOR ALL APPLICATIONS FOR PERMIT ON OR |
| | AFTER MARCH 1, 2009 IS FBC-2007 WITH 2009 SUPPLEMENTS. |
| | MANY SHEETS INCLUDING THE PLUMBING SHEET INDICATE THE |
| | DESIGN CRITERIA AS FBC-2004. PLEASE CORRECT ALL |
| | REFERENCES TO THE DESIGN CODE. SECTION 106.1.1. |
| | |
| | 2. SHT A 120.1 THE DOOR TO THE ACCESSIBLE TOILET ROOM |
| | SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR |
| | ANY FIXTURE. SECTION 11-4.22.2(1). IT APPEARS THAT THE |
| | DOOR SWINGS INTO THE CLEAR FLOOR SPACE FOR THE LAV AND |
| | THE W/C. PLEASE SHOW DOOR SWING FOR THIS TOILET ROOM. |
| | |
| | 3. SHTS A 120.1 & A 210.1 (DETAILS 8 & 9. PLEASE SHOW |
| | THE 30" BY 48" CLEAR FLOOR SPACE REQUIRED FOR THE SINK |
| | ON THE FLOOR PLAN, AND THE KNEE CLEARANCE, (27"), AND |
| | THE SINK DEPTH, (6-1/2" MAX), AS REQUIRED IN SECTIONS |
| | 11-4.24.3 & 11-4.24.4. |
| | |
| | 4. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION |
| | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |