| Plan Review Notes For Permit 09040277 |
| Permit Number |
09040277 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-17 15:12:05 | REVIEW #: 1ST | | | ACTION: PASSED W/ PROVISO | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | **PROVISO** | | | | | | 1. PROVIDE MANUFACTURER'S SUBMITTAL DATA FOR EXHAUST | | | AND SUPPLY FANS SHOWING THEY ARE DESIGNED FOR WIND | | | RESISTANCE. MECHANICAL APPLIANCES AND THAT ARE EXPOSED | | | TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND | | | PRESSURES IN ACCORDANCE WITH FBC-M 301.12. | | | | | | 2. TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED | | | TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER | | | COOKING OPERATIONS OCCUR. THE ACTIVATION OF THE EXHAUST | | | FAN SHALL OCCUR THROUGH AN INTERLOCK WITH THE COOKING | | | APPLIANCES, BY MEANS OF HEAT SENSORS OR BY MEANS OF | | | OTHER APPROVED METHODS IN ACCORDANCE WITH FBC-M | | | 507.REVISE PLANS PRIOR TO INSPECTION SHOWING HOW THE | | | EXHAUST SYSTEM WILL BE CONTROLLED FOR THIS REQUIREMENT | | | IN ACCORDANCE WITH FBC-M 506.2.1.1. | | | | | | NOTE: REVISE PLANS FOR REVIEW TO SHOW COMPLIANCE WITH | | | THESE REQUIREMENTS PRIOR TO INSPECTION. |
|