| 2009-04-16 11:19:46 | PALM HARBOR MARINA |
| | 400 NORTH FLAGLER DRIVE |
| | PERMIT # 09040257 |
| | INSTALL 1,600 LF OF 8" C-900 WITH 4" FDC ASSEMBLIES AT |
| | PALM HARBOR MARINA |
| | |
| | 1. ALL UNDERGROUND FIRE LINES AND THEIR APPURTENANT |
| | EQUIPMENT INCLUDING FIRE DEPARTMENT CONNECTIONS SHALL |
| | BE PRESSURE TESTED AT 200 PSIG FOR TWO HOURS. |
| | |
| | 2. THE FIRE DEPARTMENT CONNECTIONS SHALL BE EQUIPPED |
| | WITH KNOX-BOX LOCKING CAPS. APPLICATIONS CAN BE |
| | OBTAINED FROM THE BUREAU OF FIRE PREVENTION, 804-4724. |
| | |
| | 3. CHAIN AND LOCKS ARE REQUIRED ON THE BACKLFOW |
| | PREVENTION DEVICES FOR THE LOOPED FIRE MAIN SUPPORTING |
| | THE MARINA OPERATIONS. |
| | |
| | 4. THE NEW FIRE HYDRANTS PLANNED TO BE INSTALLED SHALL |
| | MEET UTILITY AND FIRE RESCUE STANDARDS. |
| | |
| | 5. THE EXISTING FIRE DEPARTMENT CONNECTION TO BE |
| | REMOVED SHALL NOT BE PART OF THE BUILDINGS FIRE |
| | PROTECTION SYSTEM. |
| | |
| | 6. FIRE AND PARAMEDICAL ACCESS SHALL BE MAINTAINED |
| | DURING THE PROJECT FOR EMERGENCY PURPOSES. |
| | |
| | 7. THE FIRE DEPARTMENT CONNECTION LOCATED ON THE SOUTH |
| | SIDE APPEARS TO BE FACING THE WRONG DIRECTION. |
| | |
| | 8. NO VALVES ARE PERMITTED BETWEEN THE FIRE DEPARTMENT |
| | CONNECTIONS AND THE HOSE VALVES PLANNED FOR THE DOCKS. |
| | |
| | 9. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | INSTALLATION OF THE FUEL TANK. |
| | |
| | 10. SEPARATE PLANS AND PERMITS REQUIRED FOR THE REMOVAL |
| | OF THE UNDERGROUND EXISTING FUEL TANK. |
| | |
| | APPROVED PROVISO: |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | |