| Plan Review Notes For Permit 09040254 |
| Permit Number |
09040254 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-02-10 13:36:20 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THESE COMMENTS NUMBERED TO CORRESPOND WITH COMMENTS | | | FROM PREVIOUS REVIEW CYCLE. | | | | | | 1. OK | | | | | | 2. ENERGY CODE COMPLIANCE FORM IS NOT SINGED BY THE | | | PREPARER OR THE OWNER. | | | | | | 3. NO RETURN DUCTS ARE SHOWN ON PLANS. BALANCED RETURN | | | IS REQUIRED PER FBC-R SECTION M1602.4. | | | | | | 4. OK | | | | | | 5. FANS SHOWN ON ELECTRICAL PLAN BUT NOT MECHANICAL | | | PLAN. | | | | | | 6. OK | | | | | | NOTE: WHEN PLANS WERE RESUBMITTED, THE PERMIT | | | APPLICATION WAS NOT RETURNED TO THE BUILDING | | | DEPARTMENT. ALSO, THIS APPLICATION HAD APPROXIMATELY 18 | | | MONTHS OF INACTIVITY BETWEEN SUBMISSIONS AND IS | | | THEREFORE EXPIRED IN ACCORDANCE WITH FBC-B 105.3.2. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|