| 2010-12-01 08:20:40 | BUILDING PLAN REVIEW |
| | PERMIT: 09040254 |
| | ADD: 1443 PALM BEACH LAKES BLVD |
| | CONT: O/B LARRY BROWN |
| | TEL: (561)601-9517 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | 12/01/2010 |
| | |
| | 1A) THE ORIGINAL PERMIT APPLICATION WAS NOT TURNED IN, |
| | PLEASE PROVIDE THE ORIGINALS OR SUBMIT A DUPLICATE. |
| | |
| | 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | EXISTING BUILDING CODE WITH 2009. |
| | CHAPTER 10- ADDITIONS. |
| | 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 403, 404 AND 405 OF THIS CODE (EXISTING |
| | BUILDING CODE). IN THE ORIGINAL SECTION OF THE |
| | RESIDENCE THERE IS ADDITIONAL WORK TO BE COMPLETED, |
| | RECONFIGURATION OF OF SPACE, THE ADDITION OR |
| | ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION |
| | OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY |
| | ADDITIONAL EQUIPMENT. 404.1 (EXISTING BUILDING CODE). |
| | PLEASE UPDATE PLANS TO THE 2007 FLORIDA EXISSTING |
| | BUILDING CODE SECTIONS FOR ALL PLAN REFRENCES. |
| | |
| | |
| | 1C) COMPLIED. |
| | |
| | 1D) THE AREA OF THE ADDITION IS IN A QUESTIONABLE SOILS |
| | AREA, PLEASE PROVIDE TESTING REPORT INDICATING THE |
| | MINIMUM SAFE BEARING VALUE OF THE SOILS. R401.4 SOIL |
| | TESTS. IN AREAS LIKELY TO HAVE EXPANSIVE, COMPRESSIBLE, |
| | SHIFTING OR OTHER UNKNOWN SOIL CHARACTERISTICS, THE |
| | BUILDING OFFICIAL SHALL DETERMINE WHETHER TO REQUIRE A |
| | SOIL TEST TO DETERMINE THE SOIL'S CHARACTERISTICS AT A |
| | PARTICULAR LOCATION. THIS TEST SHALL BE MADE BY AN |
| | APPROVED AGENCY USING AN APPROVED METHOD. PLANS |
| | INDICATE A.& M. ENGINEERING & TESTING, PLEASE PROVIDE |
| | (2) SIGNED & SEALED ORIGINALS. |
| | |
| | |
| | 2)COMPLIED. |
| | |
| | 3) COVERSHEET INDICATES THE LOCATION OF THIS PROJECT IN |
| | A B EXPOSURE, THE 2007 FBC-R 301.2.1.4(3) WILL PUT THIS |
| | LOCATION IN A C-EXPOSURE, THIS WILL CHANGE THE |
| | COMPONENTS AND CLADDING PRESSURES, TABLE R-301.2(3) |
| | |
| | 4) SEMI-COMPLIED. SEE ABOVE STATEMENT. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) SHEET 1.2 ON THE NEW ADDITION THE EXTERIOR DOUBLE |
| | DOORS DOES NOT INDICATE A LANDING. R311.4.3 LANDINGS AT |
| | DOORS. THERE SHALL BE A FLOOR OR LANDING ON EACH SIDE |
| | OF EACH EXTERIOR DOOR. THE EXTERIOR DOUBLE DOORS IN THE |
| | NEW ADDITION WILL NEED THE LANDING TO BE A MINIMUM OF |
| | 36 INCHES IN THE DIRECTION OF TRAVEL. |
| | |
| | 7) SHEET 1.2 INDICATES A NEW MUD ROOM, NEW OPENING |
| | BETWEEN THE GARAGE AND RESIDENCE, R309.1. R309.1 |
| | OPENING PROTECTION. OPENINGS BETWEEN THE GARAGE AND |
| | RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD DOORS NOT |
| | LESS THAN 13/8 INCHES (35 MM) IN THICKNESS, SOLID OR |
| | HONEYCOMB CORE STEEL DOORS NOT LESS THAN 13/8 INCHES |
| | (35 MM) THICK, OR 20-MINUTE FIRE-RATED DOORS. |
| | |
| | 8) SHEET 4.1 SEMI-COMPLIED, THE 2008 FBC-R SUPPLEMENTS |
| | WILL REQUIRE NOT ONLY SMOKE ALARMS BUT R313.4 WILL |
| | REQUIRE CARBON MONOXIDE ALARMS OR COMBINATION ALARMS |
| | SINCE THERE IS AN ATTACHED GARAGE. THE OPERATIONAL |
| | ALRMS MUST BE INSTALLED WITHIN 10 FEET OF EACH ROOM |
| | USED FOR SLEEPING PURPOSES. |
| | |
| | 9) SHEET 2.2 ATTIC INSULATION, PLEASE PROVIDE THE FLAME |
| | SPREAD INDEX AND SMOKE-DEVELOPMENT.R316.1 INSULATION. |
| | INSULATION MATERIALS, INCLUDING FACINGS, SUCH AS VAPOR |
| | RETARDERS OR VAPOR PERMEABLE MEMBRANES INSTALLED WITHIN |
| | FLOOR-CEILING ASSEMBLIES, ROOF-CEILING ASSEMBLIES, WALL |
| | ASSEMBLIES, CRAWL SPACES AND ATTICS SHALL HAVE A FLAME |
| | SPREAD INDEX NOT TO EXCEED 25 WITH AN ACCOMPANYING |
| | SMOKE-DEVELOPED INDEX NOT TO EXCEED 450 WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 84. |
| | |
| | 10) SHEET 1.2 & 2.1 INDICATES THE USE OF TWO NEW 11 5/8 |
| | INCH LVL BEAMS : |
| | |
| | 10) COMPLIED. |
| | |
| | 11) SHEET 2.2 DOES INDICATE COMPLIANCE WITH A ATTIC |
| | ACCESS DETAIL BUT SHEET 1.2 DOES NOT INDICATE WHERE |
| | ATTIC ACCESS WILL BE LOCATED WITHIN THE ADDITION. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED& R807.1. |
| | |
| | 12) NEW COMMENT: |
| | 12A) MISSING PRODUCT APPROVAL FOR GLASS BLOCK . |
| | |
| | 12B) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 13) SHEET 2.2 TYPICAL EXTERIOR WALL SECTION DOES NOT |
| | INDICATE ROOF AND EAVE VENETING REQUIREMENTS. R806.2 |
| | MINIMUM AREA. THE TOTAL NET FREE VENTILATING AREA SHALL |
| | NOT BE LESS THAN 1/150 OF THE AREA OF THE SPACE |
| | VENTILATED EXCEPT THAT REDUCTION OF THE TOTAL AREA TO |
| | 1/300 IS PERMITTED, PROVIDED THAT AT LEAST 50 PERCENT |
| | AND NOT MORE THAN 80 PERCENT OF THE REQUIRED |
| | VENTILATING AREA IS PROVIDED BY ****VENTILATORS**** |
| | LOCATED IN THE UPPER PORTION OF THE SPACE TO BE |
| | VENTILATED AT LEAST 3 FEET (914 MM) ABOVE THE EAVE OR |
| | CORNICE VENTS WITH THE BALANCE OF THE REQUIRED |
| | VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. AS AN |
| | ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA MAY BE |
| | REDUCED TO 1/300 WHEN A VAPOR BARRIER HAVING A |
| | TRANSMISSION RATE NOT EXCEEDING 1 PERM (5.7 ?? 10-11 |
| | KG/S ?? M2 ?? PA) IS INSTALLED ON THE WARM-IN-WINTER |
| | SIDE OF THE CEILING. |
| | |
| | 14) DOUBLE UNDERLAYMENT AS PER 905.2.2 FOR ASPHALT |
| | SHINGLES BUT THIS REQUIREMENT IS FOR ROOF SLOPES OF |
| | LESS THAN 4:12 PITCH. PLEASE MAKE NOTE. |
| | |
| | 15) STORM SHUTTERS PLEASE COMPLY WITH: |
| | |
| | PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| | MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| | 1609.1.4. |
| | |
| | FL BLD CODE 2004 SECTION 106.3.3, |
| | 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY |
| | HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT |
| | STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT |
| | TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT |
| | APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.A SAMPLE |
| | SCHEDULE IS ATTACHED. |
| | |
| | 16) W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | CALCULATED VALUE OF $101,950.00 VALUE IS LOW ADJUSTED |
| | OWES FEES PLUS STATE RADON FEES: $1,246.80. THIS IS THE |
| | FAIR MARKET VALUE. |
| | |
| | 17) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |