2010-12-01 08:20:40BUILDING PLAN REVIEW
 PERMIT: 09040254
 ADD: 1443 PALM BEACH LAKES BLVD
 CONT: O/B LARRY BROWN
 TEL: (561)601-9517
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 12/01/2010
  
 1A) THE ORIGINAL PERMIT APPLICATION WAS NOT TURNED IN,
 PLEASE PROVIDE THE ORIGINALS OR SUBMIT A DUPLICATE.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 EXISTING BUILDING CODE WITH 2009.
 CHAPTER 10- ADDITIONS.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE (EXISTING
 BUILDING CODE). IN THE ORIGINAL SECTION OF THE
 RESIDENCE THERE IS ADDITIONAL WORK TO BE COMPLETED,
 RECONFIGURATION OF OF SPACE, THE ADDITION OR
 ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION
 OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT. 404.1 (EXISTING BUILDING CODE).
 PLEASE UPDATE PLANS TO THE 2007 FLORIDA EXISSTING
 BUILDING CODE SECTIONS FOR ALL PLAN REFRENCES.
  
  
 1C) COMPLIED.
  
 1D) THE AREA OF THE ADDITION IS IN A QUESTIONABLE SOILS
 AREA, PLEASE PROVIDE TESTING REPORT INDICATING THE
 MINIMUM SAFE BEARING VALUE OF THE SOILS. R401.4 SOIL
 TESTS. IN AREAS LIKELY TO HAVE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER UNKNOWN SOIL CHARACTERISTICS, THE
 BUILDING OFFICIAL SHALL DETERMINE WHETHER TO REQUIRE A
 SOIL TEST TO DETERMINE THE SOIL'S CHARACTERISTICS AT A
 PARTICULAR LOCATION. THIS TEST SHALL BE MADE BY AN
 APPROVED AGENCY USING AN APPROVED METHOD. PLANS
 INDICATE A.& M. ENGINEERING & TESTING, PLEASE PROVIDE
 (2) SIGNED & SEALED ORIGINALS.
  
  
 2)COMPLIED.
  
 3) COVERSHEET INDICATES THE LOCATION OF THIS PROJECT IN
 A B EXPOSURE, THE 2007 FBC-R 301.2.1.4(3) WILL PUT THIS
 LOCATION IN A C-EXPOSURE, THIS WILL CHANGE THE
 COMPONENTS AND CLADDING PRESSURES, TABLE R-301.2(3)
  
 4) SEMI-COMPLIED. SEE ABOVE STATEMENT.
  
 5) COMPLIED.
  
 6) SHEET 1.2 ON THE NEW ADDITION THE EXTERIOR DOUBLE
 DOORS DOES NOT INDICATE A LANDING. R311.4.3 LANDINGS AT
 DOORS. THERE SHALL BE A FLOOR OR LANDING ON EACH SIDE
 OF EACH EXTERIOR DOOR. THE EXTERIOR DOUBLE DOORS IN THE
 NEW ADDITION WILL NEED THE LANDING TO BE A MINIMUM OF
 36 INCHES IN THE DIRECTION OF TRAVEL.
  
 7) SHEET 1.2 INDICATES A NEW MUD ROOM, NEW OPENING
 BETWEEN THE GARAGE AND RESIDENCE, R309.1. R309.1
 OPENING PROTECTION. OPENINGS BETWEEN THE GARAGE AND
 RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD DOORS NOT
 LESS THAN 13/8 INCHES (35 MM) IN THICKNESS, SOLID OR
 HONEYCOMB CORE STEEL DOORS NOT LESS THAN 13/8 INCHES
 (35 MM) THICK, OR 20-MINUTE FIRE-RATED DOORS.
  
 8) SHEET 4.1 SEMI-COMPLIED, THE 2008 FBC-R SUPPLEMENTS
 WILL REQUIRE NOT ONLY SMOKE ALARMS BUT R313.4 WILL
 REQUIRE CARBON MONOXIDE ALARMS OR COMBINATION ALARMS
 SINCE THERE IS AN ATTACHED GARAGE. THE OPERATIONAL
 ALRMS MUST BE INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
  
 9) SHEET 2.2 ATTIC INSULATION, PLEASE PROVIDE THE FLAME
 SPREAD INDEX AND SMOKE-DEVELOPMENT.R316.1 INSULATION.
 INSULATION MATERIALS, INCLUDING FACINGS, SUCH AS VAPOR
 RETARDERS OR VAPOR PERMEABLE MEMBRANES INSTALLED WITHIN
 FLOOR-CEILING ASSEMBLIES, ROOF-CEILING ASSEMBLIES, WALL
 ASSEMBLIES, CRAWL SPACES AND ATTICS SHALL HAVE A FLAME
 SPREAD INDEX NOT TO EXCEED 25 WITH AN ACCOMPANYING
 SMOKE-DEVELOPED INDEX NOT TO EXCEED 450 WHEN TESTED IN
 ACCORDANCE WITH ASTM E 84.
  
 10) SHEET 1.2 & 2.1 INDICATES THE USE OF TWO NEW 11 5/8
 INCH LVL BEAMS :
  
 10) COMPLIED.
  
 11) SHEET 2.2 DOES INDICATE COMPLIANCE WITH A ATTIC
 ACCESS DETAIL BUT SHEET 1.2 DOES NOT INDICATE WHERE
 ATTIC ACCESS WILL BE LOCATED WITHIN THE ADDITION.
 106.1.2 ADDITIONAL INFORMATION REQUIRED& R807.1.
  
 12) NEW COMMENT:
 12A) MISSING PRODUCT APPROVAL FOR GLASS BLOCK .
  
 12B) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 13) SHEET 2.2 TYPICAL EXTERIOR WALL SECTION DOES NOT
 INDICATE ROOF AND EAVE VENETING REQUIREMENTS. R806.2
 MINIMUM AREA. THE TOTAL NET FREE VENTILATING AREA SHALL
 NOT BE LESS THAN 1/150 OF THE AREA OF THE SPACE
 VENTILATED EXCEPT THAT REDUCTION OF THE TOTAL AREA TO
 1/300 IS PERMITTED, PROVIDED THAT AT LEAST 50 PERCENT
 AND NOT MORE THAN 80 PERCENT OF THE REQUIRED
 VENTILATING AREA IS PROVIDED BY ****VENTILATORS****
 LOCATED IN THE UPPER PORTION OF THE SPACE TO BE
 VENTILATED AT LEAST 3 FEET (914 MM) ABOVE THE EAVE OR
 CORNICE VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. AS AN
 ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA MAY BE
 REDUCED TO 1/300 WHEN A VAPOR BARRIER HAVING A
 TRANSMISSION RATE NOT EXCEEDING 1 PERM (5.7 ?? 10-11
 KG/S ?? M2 ?? PA) IS INSTALLED ON THE WARM-IN-WINTER
 SIDE OF THE CEILING.
  
 14) DOUBLE UNDERLAYMENT AS PER 905.2.2 FOR ASPHALT
 SHINGLES BUT THIS REQUIREMENT IS FOR ROOF SLOPES OF
 LESS THAN 4:12 PITCH. PLEASE MAKE NOTE.
  
 15) STORM SHUTTERS PLEASE COMPLY WITH:
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM
 BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.A SAMPLE
 SCHEDULE IS ATTACHED.
  
 16) W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 CALCULATED VALUE OF $101,950.00 VALUE IS LOW ADJUSTED
 OWES FEES PLUS STATE RADON FEES: $1,246.80. THIS IS THE
 FAIR MARKET VALUE.
  
 17) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved