| 2009-04-24 08:53:44 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PLEASE UPDATE PLANS BY REFERENCING THE NEW 2007 |
| | FLORIDA BUILDING CODE WITH 2009 SUPPLEMENT, WHICH HAS |
| | BEEN IN EFFECT SINCE MARCH 1, 2009. ALSO, CODE SECTIONS |
| | REFERENCED IN THE PLAN NOTES ARE FROM THE FLORIDA |
| | BUILDING CODE, MECHANICAL. THE APPLICABLE CODE FOR THIS |
| | PROJECT IS THE FLORIDA BUILDING CODE, RESIDENTIAL. |
| | PLEASE ADJUST ACCORDINGLY. |
| | |
| | 2. ENERGY CODE COMPLIANCE FORM 600A-04R HAS BEEN |
| | SUBMITTED. THIS FORM IS NO LONGER VALID FOR PERMITS |
| | APPLIED FOR ON OR AFTER MARCH 1, 2009. CODE COMPLIANCE |
| | FOR ADDITIONS SHALL BE DEMONSTRATED BY THE USE OF FORM |
| | 1100A-08 OR 1100B-08 IN ACCORDANCE WITH FBC-R SECTION |
| | N1100.0.3. |
| | |
| | 3. THERE ARE NO DUCT SIZES SHOWN ON PLANS. PLEASE SHOW |
| | THE COMPLETE DUCT DESIGN ON PLANS IN ACCORDANCE WITH |
| | FBC-B 106.1.1. |
| | |
| | 4. THE PROPOSED NEW AIR HANDLER APPEARS TO BE LOCATED |
| | IN THE NEW BATHTUB. PLEASE COORDINATE MECHANICAL AND |
| | ARCHITECTURAL FLOOR PLANS AND SHOW THE ACTUAL LOCATION |
| | OF THE AIR HANDLER, RELATED RETURNS AND SUPPLY |
| | DUCTWORK. |
| | NOTE: IF AIR HANDLER IS TO BE IN THE ATTIC, SHOW |
| | COMPLIANCE WITH THE REQUIREMENTS OF FBC-R SECTIONS |
| | M1305.1.3 FOR SERVICE ACCESS AND M1305.1.3.1 FOR |
| | LUMINAIRE AND SERVICE RECEPTACLE (COORDINATE WITH |
| | ELECTRICAL PLANS), |
| | |
| | 5. NO EXHAUST FAN IS SHOWN IN PROPOSED NEW BATHROOM. |
| | THERE ARE NO EXTERIOR WINDOWS PROPOSED FOR THIS |
| | BATHROOM. THEREFORE, MECHANICAL EXHAUST IS REQUIRED IN |
| | ACCORDANCE WITH FFBC-R SECTION R303.3. |
| | |
| | 6. ELECTRICAL PLANS DO NOT SHOW ANY POWER BEING |
| | PROVIDED FOR THE PROPOSED NEW A/C EQUIPMENT. PLEASE |
| | COORDINATE ELECTRICAL PLANS WITH MECHANICAL PLANS, |
| | SHOWING PROPERLY SIZED CIRCUITING AND OVERCURRENT |
| | PROTECTION IN ACCORDANCE WITH FBC-R SECTION M1401.1 AND |
| | FBC-B 106.1.1. |
| | |