Plan Review Notes
Plan Review Notes For Permit 09040254
Permit Number 09040254
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-17 16:01:15 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET 4.1 UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} THERE ARE ELECTRICAL PLANS PROVIDED BUT NO
 ELECTRICAL WORK IN THE DESCRIPTION ON THE APPLICATION.
 ADD DESCRIPTION TO THE APPLICATION.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 3} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN
 IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION
 ON THE APPLICATION, PROVIDE AN AIC RATING, AND LOCATE
 ALL SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A RISER
 DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND TYPE.
  
 4} THE EQUIPMENT GROUND BETWEEN THE METER AND PANEL ON
 THE RISER DIAGRAM CREATES A PARALLEL PATH TO GROUND
 WITH THE NEUTRAL AND MUST BE REMOVED.
  
 5} R313.1 SMOKE ALARMS.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS*** THERE ARE NONE OUTSIDE THE
 BEDROOMS. ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD. IF USING DETECTORS
 INDICATE THE LOCATIONS OF THE SOUNDING DEVICES.
  
 6} (E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING AND
 EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.***ONE REQUIRED IN THE FRONT.
  
 7} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.8(A)(6) GFI.
  
 8} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3)
 IF APPLICABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  