| 2009-04-17 16:01:15 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | ALL COMMENTS RELATE TO SHEET 4.1 UNLESS OTHERWISE |
| | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} THERE ARE ELECTRICAL PLANS PROVIDED BUT NO |
| | ELECTRICAL WORK IN THE DESCRIPTION ON THE APPLICATION. |
| | ADD DESCRIPTION TO THE APPLICATION. |
| | |
| | 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| | FS, RESPECTIVELY. |
| | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| | IF EXEMPTIONS APPLY. |
| | |
| | 3} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN |
| | IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION |
| | ON THE APPLICATION, PROVIDE AN AIC RATING, AND LOCATE |
| | ALL SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE, |
| | DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH |
| | ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A RISER |
| | DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND TYPE. |
| | |
| | 4} THE EQUIPMENT GROUND BETWEEN THE METER AND PANEL ON |
| | THE RISER DIAGRAM CREATES A PARALLEL PATH TO GROUND |
| | WITH THE NEUTRAL AND MUST BE REMOVED. |
| | |
| | 5} R313.1 SMOKE ALARMS. |
| | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | 1. IN EACH SLEEPING ROOM. |
| | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS*** THERE ARE NONE OUTSIDE THE |
| | BEDROOMS. ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" |
| | 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, |
| | TO AVOID CONFUSION IN THE FIELD. IF USING DETECTORS |
| | INDICATE THE LOCATIONS OF THE SOUNDING DEVICES. |
| | |
| | 6} (E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING AND |
| | EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE |
| | LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT |
| | GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE |
| | GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE |
| | DWELLING.***ONE REQUIRED IN THE FRONT. |
| | |
| | 7} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.8(A)(6) GFI. |
| | |
| | 8} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3) |
| | IF APPLICABLE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |
| | |