2009-04-28 16:26:51BUILDING PLAN REVIEW
 PERMIT: 09040254
 ADD: 1443 PALM BEACH LAKES BLVD
 CONT: O/B LARRY BROWN
 TEL: (561)601-9517
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 EXISTING BUILDING CODE WITH 2009.
 CHAPTER 10- ADDITIONS.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE (EXISTING
 BUILDING CODE). IN THE ORIGINAL SECTION OF THE
 RESIDENCE THERE IS ADDITIONAL WORK TO BE COMPLETED,
 RECONFIGURATION OF OF SPACE, THE ADDITION OR
 ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION
 OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT. 404.1 (EXISTING BUILDING CODE).
 PLEASE UPDATE PLANS TO THE 2007 FLORIDA EXISSTING
 BUILDING CODE SECTIONS FOR ALL PLAN REFRENCES.
  
  
 1C) THE ENERGY FORM 600A-2004R IS THE WRONG FORM TO USE
 WOULD BE FORM 1100-07 PRODUCED BY THE ENERGY GAUGE
 USA-FLA/ RES 2007 COMPUTER PROGRAM. 13.600.A.
 NOTE THIS FORM INDICATES THE USE OF A R=30.0 UNDER
 ATTIC INSULATION WHERE AS SHEET 2.2 INDICATES A R=19.
  
 1D) THE AREA OF THE ADDITION IS IN A QUESTIONABLE SOILS
 AREA, PLEASE PROVIDE TESTING REPORT INDICATING THE
 MINIMUM SAFE BEARING VALUE OF THE SOILS. R401.4 SOIL
 TESTS. IN AREAS LIKELY TO HAVE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER UNKNOWN SOIL CHARACTERISTICS, THE
 BUILDING OFFICIAL SHALL DETERMINE WHETHER TO REQUIRE A
 SOIL TEST TO DETERMINE THE SOIL'S CHARACTERISTICS AT A
 PARTICULAR LOCATION. THIS TEST SHALL BE MADE BY AN
 APPROVED AGENCY USING AN APPROVED METHOD.
  
  
 2) SHEET 1.2 FRAMING NOTES 16 AND 22 BOTH ARE NOTES
 THAT ARE ONLY FOR DADE-BROWARD COUNTIES, HIGH VELOCITY
 HURRICANE ZONE, PLEASE CORRECT THE CODE REFRENCES.
  
 3) SHEET 2.1 STORM SHUTTER NOTES INDICATE COMPLIANCE
 WITH SECTION 1619WHICH IN THE 2007 FBC HAS TO DO WITH
 HIGH VELOCITY HURRICANE ZONES- LIVE LOAD REDUCTIONS-
 WHICH IS EXCLUSIVELY FOR DADE AND BROWARD COUNTIES.
 PALM BEACH COUNTY AND THE CITY OF WEST PALM BEACH ARE
 IN A 140 MPH ZONE WHICH IS CONSIDERED A WIND BORNE
 DEBRIS REGION WHICH IS WHEN WINDS ARE GREATER THAN 120
 MPH, 3 SECOND GUST.
  
 4) WIND DESIGN CRITERIA FOUND ON SHEET 2.2 DOES NOT
 PROVIDE THE 3 SECOND GUST AS PART OF THE BASIC WIND
 VELOCITY R301.2(1), SEE FIGURE 301.2(4).
  
 5) SHEET A1.2 INDICATES A NEW BATHROOM IN THE ADDITION
 AND A RECONFIGURED BATH #2 BOTH APPEAR TO HAVE A TUB/
 SHOWER COMPARTMENT, NO INFORMATION HAS BEEN PROVIDED ON
 THE WALL FINISH IN THESE AREAS. R307.2 BATHTUB AND
 SHOWER SPACES. BATHTUB AND SHOWER FLOORS AND WALLS
 ABOVE BATHTUBS WITH INSTALLED SHOWER HEADS AND IN
 SHOWER COMPARTMENTS SHALL BE FINISHED WITH A
 NONABSORBENT SURFACE. SUCH WALL SURFACES SHALL EXTEND
 TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM) ABOVE THE
 FLOOR.
  
 6) SHEET 1.2 ON THE NEW ADDITION THE EXTERIOR DOUBLE
 DOORS DOES NOT INDICATE A LANDING. R311.4.3 LANDINGS AT
 DOORS. THERE SHALL BE A FLOOR OR LANDING ON EACH SIDE
 OF EACH EXTERIOR DOOR.
  
 7) SHEET 1.2 INDICATES A NEW MUD ROOM, NEW OPENING
 BETWEEN THE GARAGE AND RESIDENCE, R309.1. R309.1
 OPENING PROTECTION. OPENINGS BETWEEN THE GARAGE AND
 RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD DOORS NOT
 LESS THAN 13/8 INCHES (35 MM) IN THICKNESS, SOLID OR
 HONEYCOMB CORE STEEL DOORS NOT LESS THAN 13/8 INCHES
 (35 MM) THICK, OR 20-MINUTE FIRE-RATED DOORS.
  
 8) SHEET 4.1 IS MISSING SMOKE ALARMS: R313.1 SMOKE
 DETECTION AND NOTIFICATION. ALL SMOKE ALARMS SHALL BE
 LISTED IN ACCORDANCE WITH UL 217 AND INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE AND THE
 HOUSEHOLD FIRE WARNING EQUIPMENT PROVISIONS OF NFPA 72.
  
 HOUSEHOLD FIRE ALARM SYSTEMS INSTALLED IN ACCORDANCE
 WITH NFPA 72 THAT INCLUDE SMOKE ALARMS, OR A
 COMBINATION OF SMOKE DETECTOR AND AUDIBLE NOTIFICATION
 DEVICE INSTALLED AS REQUIRED BY THIS SECTION FOR SMOKE
 ALARMS, SHALL BE PERMITTED. THE HOUSEHOLD FIRE ALARM
 SYSTEM SHALL PROVIDE THE SAME LEVEL OF SMOKE DETECTION
 AND ALARM AS REQUIRED BY THIS SECTION FOR SMOKE ALARMS
 IN THE EVENT THE FIRE ALARM PANEL IS REMOVED OR THE
 SYSTEM IS NOT CONNECTED TO A CENTRAL STATION.
  
 R313.2 LOCATION. SMOKE ALARMS SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS:
  
 1. IN EACH SLEEPING ROOM.
  
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 9) SHEET 2.2 ATTIC INSULATION, PLEASE PROVIDE THE FLAME
 SPREAD INDEX AND SMOKE-DEVELOPMENT.R316.1 INSULATION.
 INSULATION MATERIALS, INCLUDING FACINGS, SUCH AS VAPOR
 RETARDERS OR VAPOR PERMEABLE MEMBRANES INSTALLED WITHIN
 FLOOR-CEILING ASSEMBLIES, ROOF-CEILING ASSEMBLIES, WALL
 ASSEMBLIES, CRAWL SPACES AND ATTICS SHALL HAVE A FLAME
 SPREAD INDEX NOT TO EXCEED 25 WITH AN ACCOMPANYING
 SMOKE-DEVELOPED INDEX NOT TO EXCEED 450 WHEN TESTED IN
 ACCORDANCE WITH ASTM E 84.
  
 10) SHEET 1.2 & 2.1 INDICATES THE USE OF TWO NEW 11 5/8
 INCH LVL BEAMS :
  
 10A) LOCATION : A) WHERE THE NEW ADDITION MEETS THE
 EXISTING HOUSE A NEW LVL BEAM IS POSISTIONED THERE. IT
 MAY BE ASSUMED THAT IT IS TO REPLACE THE CONCRETE BEAM
 WHERE THE LOAD BEARING WALL IS REMOVED, THE PLAN DOES
 NOT INDICATE ANY NEW FOOTINGS, COLUMNS, MASONRY OR
 STEEL IN THIS LOCATION NO ATTACHMENT DETAILS106.1.2
 ADDITIONAL INFORMATION REQUIRED, THIS AREA WOULD BE
 PART OF THE MAIN WIND FORCE RESISTING SYSTEM,
 CONTINIOUS LOAD PATH FROM FOOTER TO TRUSSES.
  
 10B) LOCATION B) NEW LVL BEAM BETWEEN THE LIVING ROOM
 AND KITCHEN. AS MENTIONED ABOVE THE PLANS DO NOT
 INDICATE IF THIS BEAM IS TO SIT ABOVE THE EXISTING
 TRUSSES REQUIRING BLOCKING TO THE WALL SYSTEM BELOW OR
 THE LVL BEAM IS BELOW THE TRUSS SYSTEM, MISSING TRUSS
 TIES AS WELL AS A SUPPORTING COLUMN, WALL OR BUCKET.
  
 11) SHEET 2.2 DOES INDICATE COMPLIANCE WITH A ATTIC
 ACCESS DETAIL BUT SHEET 1.2 DOES NOT INDICATE WHERE
 ATTIC ACCESS WILL BE LOCATED WITHIN THE ADDITION.
 106.1.2 ADDITIONAL INFORMATION REQUIRED& R807.1.
  
 12) DISCREPANCY BETWEEN 1.2 , 1.3 & 2.4. THE DOUBLE
 TRUSS ON THE RIGHT SIDE SETS BETWEEN TWO WINDOWS WHERE
 AS THE OTHERSHEETS THERE IS ONLY ONE WINDOW. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 13) SHEET 2.2 TYPICAL WALL SECTION DOES NOT INDICATE
 ROOF AND EAVE VENETING REQUIREMENTS. R806.2 MINIMUM
 AREA. THE TOTAL NET FREE VENTILATING AREA SHALL NOT BE
 LESS THAN 1/150 OF THE AREA OF THE SPACE VENTILATED
 EXCEPT THAT REDUCTION OF THE TOTAL AREA TO 1/300 IS
 PERMITTED, PROVIDED THAT AT LEAST 50 PERCENT AND NOT
 MORE THAN 80 PERCENT OF THE REQUIRED VENTILATING AREA
 IS PROVIDED BY ****VENTILATORS**** LOCATED IN THE UPPER
 PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET
 (914 MM) ABOVE THE EAVE OR CORNICE VENTS WITH THE
 BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR
 CORNICE VENTS. AS AN ALTERNATIVE, THE NET FREE
 CROSS-VENTILATION AREA MAY BE REDUCED TO 1/300 WHEN A
 VAPOR BARRIER HAVING A TRANSMISSION RATE NOT EXCEEDING
 1 PERM (5.7 ?? 10-11 KG/S ?? M2 ?? PA) IS INSTALLED ON
 THE WARM-IN-WINTER SIDE OF THE CEILING.
  
 14) NOTE THIS SAME TYPICAL SECTION INDICATES THE USE OF
 DOUBLE UNDERLAYMENT AS PER 905.2.2 FOR ASPHALT SHINGLES
 BUT THIS REQUIREMENT IS FOR ROOF SLOPES OF LESS THAN
 4:12 PITCH. THE PLANS INDICATE THIS ROOF HAVING A 5:12
 PITCH?
  
 15) ELEVATION SHEETS 1.3 & 1.4 BOTH INDICATE THE USE OF
 STORM SHUTTERS PLEASE COMPLY WITH:
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM
 BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.A SAMPLE
 SCHEDULE IS ATTACHED.
  
 16) W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 CALCULATED VALUE OF $101,950.00 VALUE IS LOW ADJUSTED
 OWES FEES PLUS STATE RADON FEES: $1,246.80. THIS IS THE
 FAIR MARKET VALUE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  