2009-04-24 12:06:43REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE UPDATE PLANS BY REFERENCING THE NEW 2007
 FLORIDA BUILDING CODE WITH 2009 SUPPLEMENT, WHICH HAS
 BEEN IN EFFECT SINCE MARCH 1, 2009.
  
 2. NO ENERGY CODE COMPLIANCE FOR HAS BEEN SUBMITTED
 WITH THIS APPLICATION. CODE COMPLIANCE FOR ADDITIONS
 SHALL BE DEMONSTRATED BY THE USE OF FORM 1100A-08 OR
 1100B-08 IN ACCORDANCE WITH FBC-R SECTION N1100.0.3.
  
 3. THERE ARE NO DUCT SIZES SHOWN FOR RETURN AIR
 TRANSFER DUCTS ON PAGE A/C 1. PLEASE SHOW HOW BALANCED
 RETURN IS TO BE ACHIEVED ON PLANS IN ACCORDANCE WITH
 FBC-R SECTION M1602.4.
  
 4. PAGE A/C 1 SHOWS AN EXHAUST FAN SCHEDULE FOR THE
 PROPOSED NEW BATHROOM. NO SUCH FAN IS SHOWN ON THIS
 PAGE. PLEASE SHOW THE LOCATION OF THIS FAN IN
 ACCORDANCE WITH FBC-B 106.1.1.
  
 5. EXHAUST FAN SCHEDULE ON PAGE A/C 1 CALLS FOR EXHAUST
 DUCT TO TERMINATE IN ROOF EAVE OR ROOF CAP. EXHAUST
 OUTLETS SHALL NOT TERMINATE AT A ROOF EAVE IF SOFFIT
 VENTS ARE USED IN ACCORDANCE WITH FBC-R SECTION
 M1501.1.
  
 6. SHOW DRYER EXHAUST ON PLANS IN ACCORDANCE WITH FBC-R
 SECTION M1502.
  