| Plan Review Notes For Permit 09040219 |
| Permit Number |
09040219 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-06-17 15:51:49 | 2007 FBC W/2009 REVISIONS | | | LEVEL 3 ALTERATIONS AND ADDITIONS TO MAIN AND GUEST | | | HOUSES | | | | | | DENIED BY BUILDING | | | | | | 1) ON THE NEW PLANS, THE EXPOSURE CATEGORIES FOR BOTH | | | STRUCTURES HAS BEEN CHANGED TO CATEGORY B. AS STATED IN | | | COMMENT #6 OF THE FIRST REVIEW, ACCORDING TO SECTION | | | R301.2.1.4.3 OF THE REVISIONS TO THE 2007 FBC BOTH | | | STRUCTURES ARE LOCATED IN EXPOSURE CATEGORY C. PLEASE | | | CORRECT. | | | NOTE: THE COMPONENT AND CLADDING PRESSURES WILL NEED TO | | | BE ADJUSTED USING THE HEIGHT AND EXPOSURE ADJUSTMENT | | | COEFFICIENTS IN TABLE R301.2(3). | | | | | | 2) THE PRODUCT APPROVAL DESIGN PRESSURES MAY BE TOO LOW | | | WHEN THE OPENING PRESSURES ARE INCREASED. PLEASE | | | REVIEW. | | | | | | NOTE: A COPY OF THE REVISIONS TO THE EXPOSURE | | | CATEGORIES AND TABLE R301.2(3) IS ATTACHED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|