Plan Review Notes
Plan Review Notes For Permit 09040219
Permit Number 09040219
Review Stop G
Sequence Number 1
Notes
Date Text
2009-04-16 14:27:18 
  
 PASSED/PROVISO -- REVISION REQUIRED. -- SECTIONS "E" &
 "F" SHALL BE 1-1/2" PER TABLE 402.4(19). -- PER
 CONVERSATION WITH ENGINEER OF RECORD, THE PIPING FOR
 AA, BB, CC, & DD WILL BE INCREASED TO 1-1/2" ALSO TO
 PROVIDE FOR A 400,000 BTU POOL HEATER.