Plan Review Notes
Plan Review Notes For Permit 09040215
Permit Number 09040215
Review Stop E
Sequence Number 3
Notes
Date Text
2009-09-20 10:25:36** DENIED **
  
 PLANS WERE REVIEWED FOR PREVIOUS COMMENTS MADE BY
 PREVIOUS REVIEWER. HOWEVER THE FOLLOWING ITEMS ARE
 NOTED AS SOME ITEMS WHICH WERE NOT PART OF PREVIOUS
 REVIEW NOTES. SOME ARE LIFE SAFETY RELATED AND SOME ARE
 NOT.
 PERMIT APPLICATION HAS NOT BEEN MADE. A PROVISO COULD
 HAVE POSSIBLY ISSUED ONLY IF PERMIT APPLICATION HAD
 BEEN MADE. SEE COMMENST BELOW, AS PERMIT APPLICATION IS
 CRITICAL TO MANY ITEMS FOR CODE COMPLIANCE.
 ** SOME OF THE BELOW ITEMS ARE LIFE SAFETY AS WELL AS
 LIFE SAFETY DEPENDING ON WHEN PERMIT APPLICATION IS
 MADE.
  
  
  
 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR BY A LICENSED
 CONTRACTOR. AS OF OCTOBER 1ST, 2009 THE 2008 NEC/
 NFPA-70 WILL GO INTO AFFECT. THIS WILL SUBSTANTIALLY
 CHANGE MANY ITEMS SHOWN ON PLANS INCLUDING ITEMS UNDER
 THE NEW CODE WHICH WILL BE CONSIDERED LIFE SAFETY BY
 NFPA.
  
 2) NOTE:
  
 3) NOTE: PLANS INDICATE SMOKE ALARMS, HOWEVER SYMBOL
 LEGEND INDICATES SMOKE DETECTORS. WHICH ONE WILL BE
 INSTALLED? IF THESE ARE IN FACT SMOKE DETECTORS THIS
 WILL AFFECT DESIGN AND INFORMATION ON PLANS FOR FA
 PANEL, DEVICES, HORNS, STROBE ETC.
 IF SMOKE ALARMS THEN PLEASE ADJUST SYMBOL LEGEND.
  
 4) NOTE: HOUSE PANEL INDICATES A TIME CLOCK FOR
 EXTERIOR LIGHTING CONTROLS. PLEASE SEE 13-415.AB.1.4.
 ALL EXTERIOR LIGHTING SHALL BE EITHER OF THE TWO
 METHODS IN SECTION. A STANDARD TIME CLOCK IS NOT
 ACCEPTABLE.
  
 5) NOTE: ** NOTED: RISER INDICATES FOOTER STEEL TO BE
 PART OF THE GROUNDING ELECTRODE SYSTEM. THIS IS AN
 EXISTING BUILDING; IF THIS ATTACHMENT DOES NOT EXIST IT
 WOULD NOT BE REQUIRED TO ACCESS STEEL OF EXISTING
 FOOTING. THIS WOULD ACTUALLY AFFECT THE STRUCTURAL
 INTEGRITY OF THE EXISTING FOOTERS. IF SHOWN ON RISER
 THEN IT WILL BE REQUIRED. 250.50
  
 ** ONCE AGAIN PERMIT APPLICATION HAS NOT BEEN MADE.
 2008 NEC WILL CHANGE MANY ITEMS.
  
  
 ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT
 INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS
 REQUIRED.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  