Plan Review Notes
Plan Review Notes For Permit 09040215
Permit Number 09040215
Review Stop G
Sequence Number 2
Notes
Date Text
2009-08-05 15:57:29DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 SEPARATE GAS PERMIT:
  
 ****FROM PREVIOUS REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE PIPE LENGTH IS NOT
 INDICATED ON THE SECTIONS OF PIPE FROM THE METER DOWN
 TO THE HORIZONTAL PIPING, FROM THE HORIZONTAL PIPING TO
 THE WATER HEATERS, FROM THE HORIZONTAL TO THE RISER UP
 TO THE SECOND FLOOR AND FROM THE SECOND FLOOR RISER
 OVER TO THE SECOND FLOOR RANGE IS NOT SHOWN.
  
 2. OK
 3. OK
 4. OK
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2005 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, TO BE VERIFIED WHEN COMMENT NUMBER
 1 IS ADDRESSED.
  
 6. N/A
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2007 FUEL GAS CODE SEC. 402.2 & G2413.2.
 IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED, BUT IF THE PRESSURE DELIVERED IS 2
 PSI THEN REGULATORS WILL BE REQUIRED AT EACH APPLIANCE
 WITH THE SHUT OFF VALVE INSTALLED IMMEDIATELY AHEAD OF
 EACH REGULATOR. SECTIONS 409.4 & 410.1.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & G2426 THRU G2429.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED FOR THE
 WATER HEATERS. THERE ARE TWO WINDOWS IN CLOSE PROXIMITY
 OF THE WATER HEATERS.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & G2413.2.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 10. N/A
 11. N/A
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved