| Date |
Text |
| 2009-08-05 15:57:29 | DENIED |
| | REFERENCE: |
| | FBC-2007 FUEL GAS |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE |
| | SEPARATE GAS PERMIT: |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2007 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT THE PIPE LENGTH IS NOT |
| | INDICATED ON THE SECTIONS OF PIPE FROM THE METER DOWN |
| | TO THE HORIZONTAL PIPING, FROM THE HORIZONTAL PIPING TO |
| | THE WATER HEATERS, FROM THE HORIZONTAL TO THE RISER UP |
| | TO THE SECOND FLOOR AND FROM THE SECOND FLOOR RISER |
| | OVER TO THE SECOND FLOOR RANGE IS NOT SHOWN. |
| | |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2005 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED, TO BE VERIFIED WHEN COMMENT NUMBER |
| | 1 IS ADDRESSED. |
| | |
| | 6. N/A |
| | |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2007 FUEL GAS CODE SEC. 402.2 & G2413.2. |
| | IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ****RESPONSE NOTED, BUT IF THE PRESSURE DELIVERED IS 2 |
| | PSI THEN REGULATORS WILL BE REQUIRED AT EACH APPLIANCE |
| | WITH THE SHUT OFF VALVE INSTALLED IMMEDIATELY AHEAD OF |
| | EACH REGULATOR. SECTIONS 409.4 & 410.1. |
| | |
| | 8. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2007 FUEL GAS CODE |
| | SECS. 502 THRU 505 & G2426 THRU G2429. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED FOR THE |
| | WATER HEATERS. THERE ARE TWO WINDOWS IN CLOSE PROXIMITY |
| | OF THE WATER HEATERS. |
| | |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2007 FUEL GAS CODE SEC 402.2 & G2413.2. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | |
| | 10. N/A |
| | 11. N/A |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |