| Plan Review Notes For Permit 09040215 |
| Permit Number |
09040215 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-08-14 19:17:34 | *****UNSAT***** | | | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN: | | | | | | 1. THIS COMMENT FROM THE PREVIOUS REVIEW HAS BEEN | | | ADDRESSED. "THE PROJECT SITE ADDRESS SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET." | | | | | | 2. (THIS IS A NEW COMMENT) PROVIDE A 2A:10BC RATED FIRE | | | EXTINGUISHER WHICH SATISFIES THE 75' TRAVEL DISTANCE. | | | THIS REQUIREMENT MAY BE ACCOMPLISHED BY EITHER | | | INSTALLING FIRE EXTINGUISHER(S) IN THE COMMON AREA OF | | | THE BUILDING ACCESSIBLE TO ALL FOUR DWELLING UNITS OR | | | INSTALLING A FIRE EXTINGUISHER IN EACH DWELLING UNIT. | | | | | | 3. THE OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN | | | SATISFIED. | | | | | | 4. AN APPLICATION FOR PERMIT IS ON FILE. | | | | | | 5. NO OTHER ADDITIONS, DELETIONS, OR CHANGES (OTHER | | | THAN THOSE AS A RESULT OF THE PLAN EXAMINERS' COMMENTS) | | | ARE MADE TO TO THIS EXISTING PLAN. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|